6.3
Assign outputs
When configuration parameter SPLIT is inactive, the following applies:
Assignment rules
without SPLIT
•
1 of the 3 function types MIN, MAX and AVR can be assigned to each output
(parameter MOD1AOx / TYP AOx).
•
Each of the assigned function types considers all active inputs.
•
The value range of output Y1 can be specified with parameters MINVAL1,
MAXVAL1. The same applies to output Y2 (MINVAL2, MAXVAL2).
Example: DC 0…10 V corresponds to 0…50 °C.
When SPLIT is active, the following applies:
Assignment rules
with SPLIT
•
1 of the 3 function types MIN, MAX and AVR can be assigned to each output
(parameter MOD1AOx / TYP AOx).
•
The first output (AO1) with its function type considers input range IN 1 – IN 2.
•
The second output (AO2) with its function type considers input range IN 3 – IN 5.
•
The value range of output Y1 can be specified with parameters MINVAL1,
MAXVAL1. The same applies to output Y2 (MINVAL2, MAXVAL2).
Example: DC 0…10 V corresponds to 0…50 °C.
6.4
Settings
Path:
COMMIS > CONF > MIN-MAX-AVR
Configuration
Display Name
Settings
IN 1
Input 1
---, X1...X5
IN 2
Input 2
---, X1...X5
IN 3
Input 3
---, X1...X5
IN 4
Input 4
---, X1...X5
IN 5
Input 5
---, X1...X5
SPLIT
Inputs segregated
NO, YES
MOD1AO1 Min-max average output 1
---, Y1, Y2
MOD1AO2 Min-max average output 2
---, Y1, Y2
TYP AO1
Function type output 1
MIN, MAX, AVR
TYP AO2
Function type output 2
MIN, MAX, AVR
Path:
... > PARA > MIN-MAX-AVR
Setting values
Display Name
Range
Factory setting
TEMP
% or 0
FACTIN1
Factor input 1
1…100
1
1
MINVAL1
Value low 1
−
999.9…
+
9999.9
−
50 0
MAXVAL1
Value high 1
−
999.9…
+
9999.9 250
100
MINVAL2
Value low 2
−
999.9…
+
9999.9
−
50 0
MAXVAL2
Value high 2
−
999.9…
+
9999.9 250
100
26 / 46
Siemens
SEZ220 signal converter
CE1P5146en
Building Technologies
Function block MIN-MAX-AVR
02.06.2008