Connections and functions,
continued
AO 2 inverted
MAXPOS2
Y
[ % ]
x
51
46
D
03
MINPOS2
MINVAL2
MAXVAL2
0
100
8.2
Assign inputs and outputs
The function block is activated through the following assignments:
Activate function block
•
Input
IN X,
and
•
At least 1 of the 2 outputs AO x.
You can define the measuring or value range of IN X when configuring the
associated input Xx (see Section 5).
8.3
Settings
Path:
COMMIS > CONF > 2X-INV
Configuration
Display Name
Settings
IN X
Preselection external
---, X1...X5
AO 1
Modulating output 1
---, Y1, Y2
AO 2
Modulating output 2
---, Y1, Y2
Path:
... > PARA > 2X-INV
Setting values
Display Name
Range
Factory setting
MINPOS1
Dew point
0...100 %
0
MAXPOS1
Positioning signal max 1
0...100 %
100
MINVAL1
Value low 1
−
50…
+
9999.9 0
MAXVAL1
Value high 1
−
50…
+
9999.9 50
INVERS1 Inversion
1
NO,
YES
NO
MINPOS2
Positioning signal min 2
0...100 %
0
MAXPOS2
Positioning signal max 2
0...100 %
100
MINVAL2
Value low 2
−
50…
+
9999.9 0
MAXVAL2
Value high 2
−
50…
+
9999.9 50
INVERS2 Inversion
2
NO,
YES
NO
Path:
INFO
Display values
Display Name
Comments
AO 1
Modulating output 1
0...100 %
AO 2
Modulating output 2
0...100 %
Path:
COMMIS > TEST
Wiring test
Display Name
Positions
AO 1
Modulating output 1
---, 0...100 %
AO 2
Modulating output 2
---, 0...100 %
32 / 46
Siemens
SEZ220 signal converter
CE1P5146en
Building Technologies
Function block 2X-INV
02.06.2008