background image

Document No. 129-399 

Installation Instructions  

January 18, 2008 

 

CAUTION: 

 

Turning the dial in the counterclockwise 
direction may loosen the potentiometer 
locking screw. 

 

Electrical Connection 

SQM5… actuators are equipped with two removable 
conduit connection plates located on the upper 
corner of the gear housing. Each plate is provided 
with two threaded connections for 1/2-inch NPSM  
conduit connectors. The use of flexible 14 gauge or 
smaller stranded wire is recommended. 

NOTE:

  SQM5… Actuators require a single-source, 

single-phase power supply. 

 

EA0555R3

AGA56.1A97

MAN

AUTO

1

2

11

21

M

I

II

III

IV

V

12

22

13

23

14

15

24

25

3

4

5

"Economy"/Fully closed
Minimum/Low fire

Maximum/High fire

Auxilliary

IV...VI

III

II

I

1

2

13

21 12

N

VI

16

26

6

51

A

actuator switch

wire leads

L

Z

shown in
auto position

ASZ...

(1000 Ohm)

b

a

c

 

Figure 4.  Basic Functional Diagram of AGA56.1… 

 

0

A

Z

L

A

Z

L

AUTO.

MAN.

AGA56.1A97

EA0554R3

 

Figure 5  AGA56.1A97 Terminal and Auto-Manual Board. 

 

Commissioning 

Manual Operation 

1. 

Set the AUTO/MAN switch in the MAN position. 

2. 

Connect ground to the screw located below the 
shaft release button. 

3. 

Connect neutral to the double terminal block, 
located on the left side of the gray switch housing. 

4. 

Only terminal "L" must be powered to enable 
manual operation. The actuator can now be driven 
to the maximum position (switch cam I) or the fully 
closed "economy position" (switch cam II) by using 
the toggle switch located to the left of the 
AUTO/MAN switch. 

Automatic Operation 

1.  Set the AUTO/MAN switch in the AUTO position. 

2.  Connect ground to the screw located below the shaft 

release button. 

3.  Connect neutral to the double terminal block, located 

on the left side of the gray switch housing. 

4.  Connect line voltage to terminal A to drive the 

actuator in the opening direction. 

5.  Connect line voltage to terminal Z to drive the 

actuator in the closing direction. 

CAUTION: 

 

Actuator damage will result if power is supplied 
to terminals A and Z simultaneously. 

Siemens Building Technologies, Inc.

 

Page 3

 

of

 

4

 

Содержание sqm50

Страница 1: ...lowed as specified Installation Cover Removal Use a Phillips screwdriver to loosen the two screws on the actuator cover corners See Figure 1 Lift the screws and raise the cover See Figure 2 EA0564R1 EA0568R1 Figure 1 Figure 2 Rotational Direction Verification Actuator model numbers that end with R are factory configured for clockwise cw minimum to maximum rotation when facing the gear end of the a...

Страница 2: ...A3 actuators have a 90 potentiometer and the switches must be adjusted between 0 and 90 SQM5x xxxRxA4 actuators have a 135 potentiometer and the switches must be adjusted between 0 and 135 Shaft Adjustment The actuator shaft can be disengaged by pressing the silver shaft release button The button is located above the grounding screw under the hinged terminal protection cover and to the right of th...

Страница 3: ...54R3 Figure 5 AGA56 1A97 Terminal and Auto Manual Board Commissioning Manual Operation 1 Set the AUTO MAN switch in the MAN position 2 Connect ground to the screw located below the shaft release button 3 Connect neutral to the double terminal block located on the left side of the gray switch housing 4 Only terminal L must be powered to enable manual operation The actuator can now be driven to the ...

Страница 4: ...4 6 1 3 16 30 2 1 16 52 5 2 1 16 52 5 1 7 16 36 EA0522R2 5 1 4 133 7 1 16 180 2 1 16 52 5 2 1 16 52 5 3 8 10 Pg 13 5 1 2 NPSM M6 7 1 16 180 5 16 8 5 6 7 16 164 5 16 7 5 1 16 1 1 8 3 5 EA0542R3 4 7 16 113 3 1 8 80 5 3 16 132 M6 Figure 8 SQM5x xxxRxx Dimensions in Inches Millimeters Information in this publication is based on current specifications The company reserves the right to make changes in s...

Отзывы: