background image

Document No. 129-401 
Installation Instructions 
January 18, 2008 

10

0

30

50

0

0

10

0

30

50

50

10

10

0

30

70

0

10

0

30

50

 CAM DRUM

RELEASE BUTTON

GEAR END

EA0561R3

ACTUATOR

POSITION SCALE

SWITCH CAM I

SET AT MAXIMUM

SWITCH CAM II

SET AT ZERO ("ECONOMY")

SWITCH CAM III

SET AT MINIMUM

ACTUATOR POSITION

INDICATING POINTER

CAM DRUM

ASZ... (1000 Ohm)

FEEDBACK POTENTIOMETER

DIAL POINTER

ACTUATOR POSITION

INDICATING DIAL

SINGLE SWITCH

CAM POINTER

DOUBLE SWITCH CAM POINTER

 

Figure 3.  Component Identification on the Cam Drum Side of the SQM5…Actuator.

NOTE: 

The single switch cam pointers are used 

 

together with the black scales when 

 

configured for ccw operation. 

 

The double switch cam pointers are used 
together with the red scales when 
configured for cw operation.  

 

The individual switch cams can be adjusted by hand 
or with the use of the tool attached to the outside of 
the hinged switch terminal protection lid. 

The adjustable range of the switches is limited by 
the potentiometer range. 

 SQM5x.xxxRxZ

3

 actuators have a 90° potentiometer 

and the switches must be adjusted between 0° and 
90°. 
 
SQM5x.xxxRxZ

4

 actuators have a 135° 

potentiometer and the switches must be adjusted 
between 0° and 135°.  

Shaft Adjustment

 

The actuator shaft can be disengaged by pressing 
the silver shaft release button. The shaft release 
button is located above the grounding screw, under 
the hinged terminal protection cover, and to the right 
of the auto/manual switch. After pressing the shaft 
release button in and slightly upward, the shaft can 

be manually rotated. After the shaft has been 
manually aligned to the closed position, re-engage 
the shaft by pushing the shaft release button 
downwards. 

Cam Drum Adjustment 

Once the shaft has been set to the closed position, 
the cam drum must be manually aligned by pressing 
and holding the black cam drum release button (see 
Figure 3). Rotate the cam drum until the “0” mark on 
the actuator position scale (left scale on the cam 
drum) is aligned with the gray actuator position 
indicating pointer. 
 

Position Indicating Dial Adjustment 

The actual position of the SQM5… actuator is 
indicated by the gray actuator position indicating 
pointer (see Figure 3). The position is also displayed 
by the indicating dial through the housing’s window. 
Ensure that the actuator position indicating dial is 
aligned with the actuator position scale. If 
necessary, rotate the dial in the clockwise direction. 
 

 

CAUTION: 

 

Turning the dial in the counterclockwise 
direction may loosen the potentiometer 
locking screw. 

Page 2 of 6

 

Siemens Building Technologies, Inc.

 

Содержание SQM50 series

Страница 1: ...cedures as specified Installation Cover Removal Use a Phillips screwdriver to loosen the two screws on the actuator cover corners See Figure 1 Lift the screws and raise the cover See Figure 2 EA0564R1 EA0568R1 Figure 1 Figure 2 Rotational Direction Verification Actuator model numbers that end with R are factory configured for clockwise cw minimum to maximum rotation when facing the gear end of the...

Страница 2: ...en 0 and 135 Shaft Adjustment The actuator shaft can be disengaged by pressing the silver shaft release button The shaft release button is located above the grounding screw under the hinged terminal protection cover and to the right of the auto manual switch After pressing the shaft release button in and slightly upward the shaft can be manually rotated After the shaft has been manually aligned to...

Страница 3: ...marked 51 during high voltage testing Reconnect it to the grounding terminal after the test EA0557R6 AGA56 9 Y0 3 25 50 75 MAX MIN 0 o r 1 2 m A 1 0 m A 8 m A 6 m A 1 4 m A 1 6 m A 1 8 m A 25 50 75 MAX 4 m A 2 0 m A MIN Z F POS POS LIN Y0 3 Y0 3 POS 2 1 J1 J2 2 REG MAX MIN Y0 3 MIN MAX OPE MAX MIN MAX MIN SHIFT LIN 1 2 V 135 Ohm 4 20 mA 0 10 V 0 20 mA 4 20 mA 0 10 V 0 20 mA 4 20 mA 1 2 3 11 21 M I...

Страница 4: ...e actuator to the maximum high fire purge position Once the maximum position is reached terminal 11 on switch I will be energized to provide position feedback 7 Connect power to terminal ZL to drive the actuator to the minimum low fire position Once the minimum position is reached terminal 23 on switch III will be energized to provide position feedback Adjustment of switch III will determine the l...

Страница 5: ...ional movements when subjected to lower input signals and larger rotational movements when subjected to higher input signals For example based on a 90 modulating range a change in input signal from 4 to 8 mA will cause a rotational movement of 11 25 An equal change from 16 to 20 mA will cause a rotational movement of 45 Thus with the linearization function enabled the change in flow is closely pro...

Страница 6: ...55 5 ALLOW 3 5 SPACE FOR COVER REMOVAL 1 3 16 30 5 8 16 2 5 8 67 1 4 6 1 3 16 30 2 1 16 52 5 2 1 16 52 5 1 7 16 36 EA0522R2 5 1 4 133 7 1 16 180 2 1 16 52 5 2 1 16 52 5 3 8 10 Pg 13 5 1 2 NPSM M6 7 1 16 180 5 16 8 5 6 7 16 164 5 16 7 5 1 16 1 1 8 3 5 EA0542R3 4 7 16 113 3 1 8 80 5 3 16 132 M6 Figure 6 SQM5x xxxRxx Dimensions in Inches Millimeters Information in this publication is based on current...

Отзывы: