Document No. 129-401 
Installation Instructions 
January 18, 2008 

 

M

U4

Y1

Y2

Y3

Y0

0

MAN.

AUTO.

L

Z

A

L1

Z L

N

P

3-POSITION

SWITCH

JUMPERS

OPE
M A X

M I N

1
2

J1

LIN

1
2

J2

U1...U3

MAX     POS     MIN

POT. METERS

AGA56.9A...

U 1

2

3

M

ZF

M

U

U

EA0558R3

Figure 5.  AGA56.9…… Terminal and Trim Potentiometer Boards. 

 

Commissioning 

Manual Operation 

1. 

Set the AUTO/MAN switch in the MAN position. 

2. 

Connect ground to the screw located below the 
shaft release button. 

3. 

Connect neutral to terminal N. 

4. 

Only terminal "L" must be powered to enable 
manual operation. The actuator can now be driven 
to the maximum (high fire) position (switch cam I) or 
the fully closed "economy position" (switch cam II) 
by using the toggle switch located to the left of the 
AUTO/MAN switch. 

Automatic Operation 

1.  Set the AUTO/MAN switch in the AUTO position. 

2.  Connect ground to the screw located below the shaft 

release button. 

3.  Connect neutral to terminal N. 

4.  Connect line voltage at all times to terminal L to 

provide power to the electronic circuit board. 

5.  Connect line voltage to terminal L1 to provide power 

when modulating. Connect line voltage to Terminal 
L1 

only

 after removing power on terminals A and Z 

(otherwise actuator damage may result). 

6.  Connect line voltage to terminal A to drive the 

actuator to the maximum (high fire purge) position. 
Once the maximum position is reached, terminal 11 
(on switch I) will be energized to provide position 
feedback. 

7.  Connect power to terminal ZL to drive the actuator to 

the minimum (low-fire) position. Once the minimum 

position is reached, terminal 23 (on switch III) will be 
energized to provide position feedback. Adjustment 
of switch III will determine the low-fire stop position. 
Switch III (low fire) must be set at a higher position 
than switch II (fully closed). Terminal ZL may be 
energized 

only

 after removing power from terminals 

A, Z, 13, and LR. 

8.   Connect line voltage to terminal Z to drive the 

actuator to the fully closed/economy position  
(switch II).  

 

CAUTION: 

 

Under no circumstances should terminals A 
and Z be powered at the same time. Actuator 
damage will occur. 

9.  Connect the input control signal wires to the 

appropriate terminals. See Figure 4. 

Modulation Adjustment 

The blue trim potentiometers allow the adjustment of 
the minimum (zero) and maximum (span) positions. 
The factory setting of the MIN trim potentiometer is 
rotated fully counter clockwise. 
The factory setting of the MAX trim potentiometer is 
rotated fully clockwise. 

Zero Adjustment 

Set the OPE/MAX/MIN slide switch to MIN (see 
Figure 5). The blue MIN trim potentiometer can now 
be gently adjusted to the required minimum position. 
Return the OPE/MAX/MIN slide switch to OPE for 
operation. 

Page 4 of 6

 

Siemens Building Technologies, Inc.

 

Содержание SQM50 series

Страница 1: ...cedures as specified Installation Cover Removal Use a Phillips screwdriver to loosen the two screws on the actuator cover corners See Figure 1 Lift the screws and raise the cover See Figure 2 EA0564R1 EA0568R1 Figure 1 Figure 2 Rotational Direction Verification Actuator model numbers that end with R are factory configured for clockwise cw minimum to maximum rotation when facing the gear end of the...

Страница 2: ...en 0 and 135 Shaft Adjustment The actuator shaft can be disengaged by pressing the silver shaft release button The shaft release button is located above the grounding screw under the hinged terminal protection cover and to the right of the auto manual switch After pressing the shaft release button in and slightly upward the shaft can be manually rotated After the shaft has been manually aligned to...

Страница 3: ...marked 51 during high voltage testing Reconnect it to the grounding terminal after the test EA0557R6 AGA56 9 Y0 3 25 50 75 MAX MIN 0 o r 1 2 m A 1 0 m A 8 m A 6 m A 1 4 m A 1 6 m A 1 8 m A 25 50 75 MAX 4 m A 2 0 m A MIN Z F POS POS LIN Y0 3 Y0 3 POS 2 1 J1 J2 2 REG MAX MIN Y0 3 MIN MAX OPE MAX MIN MAX MIN SHIFT LIN 1 2 V 135 Ohm 4 20 mA 0 10 V 0 20 mA 4 20 mA 0 10 V 0 20 mA 4 20 mA 1 2 3 11 21 M I...

Страница 4: ...e actuator to the maximum high fire purge position Once the maximum position is reached terminal 11 on switch I will be energized to provide position feedback 7 Connect power to terminal ZL to drive the actuator to the minimum low fire position Once the minimum position is reached terminal 23 on switch III will be energized to provide position feedback Adjustment of switch III will determine the l...

Страница 5: ...ional movements when subjected to lower input signals and larger rotational movements when subjected to higher input signals For example based on a 90 modulating range a change in input signal from 4 to 8 mA will cause a rotational movement of 11 25 An equal change from 16 to 20 mA will cause a rotational movement of 45 Thus with the linearization function enabled the change in flow is closely pro...

Страница 6: ...55 5 ALLOW 3 5 SPACE FOR COVER REMOVAL 1 3 16 30 5 8 16 2 5 8 67 1 4 6 1 3 16 30 2 1 16 52 5 2 1 16 52 5 1 7 16 36 EA0522R2 5 1 4 133 7 1 16 180 2 1 16 52 5 2 1 16 52 5 3 8 10 Pg 13 5 1 2 NPSM M6 7 1 16 180 5 16 8 5 6 7 16 164 5 16 7 5 1 16 1 1 8 3 5 EA0542R3 4 7 16 113 3 1 8 80 5 3 16 132 M6 Figure 6 SQM5x xxxRxx Dimensions in Inches Millimeters Information in this publication is based on current...

Отзывы: