Connection diagrams and connection terminals
(cont’d)
2-position version with 2 end switches and 3 auxiliary switches, 1 relay
xx
xx
X3
X2
X1
1
2 3
K-A
IV
III
5
M
II
I
VI
1 2
3
4
1
2
3
4
5
6
a1
7
78
17
d1
6
/1
013
Mains voltage terminals
Dimensioning
X1-1
Move to ignition position
(III)
Input
AC 120 V / AC 230 V
max. 1 A, cos
>0.9
X1-2
Auxiliary switch AUX (IV)
NO contact
Output
AC 120 V / AC 230 V
max. 1 A, cos
>0.9
X1-3
Auxiliary switch AUX (IV)
Input
AC 120 V / AC 230 V
max. 1 A, cos
>0.9
X1-4
Neutral
AC 120 V / AC 230 V
max. 1 A, cos
>0.9
X1-5
Closing (II)
Input
AC 120 V / AC 230 V
max. 1 A, cos
>0.9
X1-6
Opening (I)
Input
AC 120 V / AC 230 V
max. 1 A, cos
>0.9
X2-1
Mains voltage
Input
AC 120 V / AC 230 V
max. 1 A, cos
>0.9
X2-2
Open / close relay
Input
AC 120 V / AC 230 V
max. 1 A, cos
>0.9
X2-3
Open position reached (I)
Output
AC 120 V / AC 230 V
max. 0.3 A, cos
>0.8
X2-4
Close position reached (II)
Output
AC 120 V / AC 230 V
max. 0.3 A, cos
>0.8
X2-5
Ignition position reached
(III)
Output
AC 120 V / AC 230 V
max. 0.3 A, cos
>0.8
X3-1
Auxiliary switch AUX (VI)
NO contact
Output
AC 120 V / AC 230 V
max. 1 A, cos
>0.9 **
X3-2
Auxiliary switch AUX (VI)
NC opener
Output
AC 120 V / AC 230 V
max. 1 A, cos
>0.9 **
X3-3
Auxiliary switch AUX (VI)
Input
AC 120 V / AC 230 V
max. 1 A, cos
>0.9 **
Notice!
** When connecting a fuel valve:
Max. 0.3 A, cos
φ
>0.8 inductive.
See SQM4x.x4xxxx in this chapter.
SQM4x.x7xxxx
Range adjustment