12/26
Building Technologies Division
CC1N7817en
24.02.2015
Technical Data
Operating voltage
- SQM4x.xxxA1…
- SQM4x.xxxA2…
- SQM4x.xxxR1…
AC 120 V -15%/+10%
AC 230 V -15%/+10%
AC 120 V -15%/+10%
Operating frequency
50…60 Hz ±6%
Drive motor
Synchronous motor
Power consumption
10 VA
Operating angle
Between 0° and max. 90° or between 0°
and max. 135°, depending on the type
Mounting position
Optional
Degree of protection
IP66
Nema 4
(only for types with UL / CSA certification:
In process)
Safety class
I
External overload fuse
Max. 6.3 AT (slow) to DIN EN 60127-2/5
Internal overload fuse
2 AT (slow), depending on the type, non-
exchangeable
Cable entry
2 x M16 without thread or
2 x ½” NPT thread, depending on the type
Wire cross-sectional area of the
connecting wires, including earth terminal
(PE)
0.5...2.5 mm²
Direction of rotation
Facing the shaft end (mounting surface):
SQM40...
Counterclockwise
(CCW)
SQM41...
Clockwise
(CW)
Torque
2.5 Nm / 5 Nm / 10 Nm / 18 Nm,
depending on type
1)
Torque tolerance
-25%
Each valid at the tolerance limits of
temperature and operating voltage
Holding torque
50%
Of the torque for types with 5 Nm, 10 Nm,
and 18 Nm torque
36%
Of the torque for types with 2.5 Nm torque
Running time
5 s, 15 s, 30 s and 65 s, depending on
type
1)
Running time tolerance
+10%
Pause time at change in direction of
rotation, zero-current state
>100 ms
End and auxiliary switches
Type
Switching
voltage
Switching
capacity
To DIN 41636
AC 24...250 V
See specifications in chapter
Connection
diagrams
Number of end switches
2
Number of auxiliary switches
Max. 4, depending on type
Drive shaft
Supplied as standard, non-exchangeable
Weight
Approx. 2 kg
Temperature of the mounting surface
Max. 60 °C
1) Specifications apply to ambient temperatures of 23 °C and a mains voltage of AC 120 V or
AC 230 V and a mains frequency of 50 Hz. With a mains frequency of 60 Hz, the running times are
approx. 17% shorter. The torques lower by the same rate
General unit data