background image

SKP70…U.. Air/Gas Ratio Controlling Actuators

Technical Instructions

155-516P25

Rev. 2, December, 1998

Siemens Building Technologies, Inc

P

P

P

Pa

a

a

age 

ge 

ge 

ge 5

5

5

5    o

o

o

of 

f 9

9

9

9

Landis Division

O

O

O

Op

p

p

pe

e

e

errrra

a

a

attttiiiio

o

o

on

n

n

n, 

, c

c

c

co

o

o

on

n

n

ntttt’’’’d

d

d

d....

The SKP70… also has the ability to compensate for pressure disturbances in the
combustion chamber. Typically in installations where the resistance in the combustion
chamber and the stack is constant, the combustion chamber pressure changes in
proportion to the gas and air pressures as the burner output is varied. Under these
circumstances it is generally not necessary to compensate for the combustion chamber
pressure. If however, the combustion chamber pressure does not change in proportion
to the gas or air pressure (as is the case with flue gas dampers or flue gas fans),
connection of the combustion chamber pressure to the regulator is necessary. This
compensation circuit should also be employed when pressure shocks or vibrations
disrupts the burner startup phase.

The SKP70… regulator gas diaphragm incorporates an additional safety diaphragm. In
the event of a gas diaphragm rupture, the reinforced safety diaphragm serves to prevent
excessive leakage of gas. With the SKP70…, leakage due to diaphragm rupture stops
when the burner shuts off and the valve is closed. (Conventional regulators continue to
leak and therefore have to be vented to the outdoors.)

N

N

N

No

o

o

otttte

e

e

e:::: To avoid oscillation, do not oversize the VG… valve. (

See

 Technical Instruction No.

155-512P25.)

F

F

F

Fiiiig

g

g

gu

u

u

urrrre 

e 1

1

1

1. 

.     S

S

S

SK

K

K

KP

P

P

P7

7

7

70

0

0

0…

…U

U

U

U..... 

. O

O

O

Op

p

p

pe

e

e

errrra

a

a

attttiiiio

o

o

on

n

n

n....

IIIIn

n

n

ns

s

s

stttta

a

a

all

ll

ll

lla

a

a

attttiiiio

o

o

on

n

n

n

W

W

W

WA

A

A

AR

R

R

RN

N

N

NIIIIN

N

N

NG

G

G

G::::

All installation must be carried out by qualified
personnel only.

The SKP70… actuator is directly coupled to the VG… series valve body by four bolts
found in the terminal box of the actuator. The square mounting flange can be rotated in
steps of 90

o

 providing four different mounting positions. The actuator can be mounted in

any position with the diaphragm vertically oriented but cannot be mounted in the upside
down position. The actuator can be mounted or replaced while the gas valve is installed
and under pressure. The actuator should be mounted so that the stroke position
indicator is clearly visible.

The SKP70… actuator packing contains an electrical conduit adapter to match with
½”-14 NPSM conduit. If the actuator is equipped with an auxiliary or proof of closure
switch, two such adapters are included.

N

N

N

No

o

o

otttte

e

e

e:::: Wiring must conform with local electrical codes.

Содержание SKP Series

Страница 1: ...he combustion air pressure without the need for an additional constant gas pressure regulator Since three functions safety shutoff constant pressure regulation and air gas ratio control can be performed by a single valve fewer components and fittings are required to assemble a gas train reducing both the size and the weight of the gas train significantly The total pressure drop across the gas trai...

Страница 2: ... fitting See Figure 4 AGA78 A motorized pressure reducing control SQN37 can also be installed in the air impulse line to continuously optimize combustion when used in conjunction with an oxygen trim system P P P Pr r r ro o o odu du du duc c c ct t t t N N N Nu u u um m m mb b b be e e er r r rs s s s T T T Ta a a ab b b bl l l le e e e 1 1 1 1 P P P Pr r r ro o o od d d du u u uc c c ct t t t N N...

Страница 3: ...imensions See Figure 6 Specification for valves See gas valve Technical Instruction No 155 512P25 Connections Conduit connection inch NPSM adapter Gas air combustion chamber pressure connections NPT Operating characteristics Output force 100 lb 450 N Maximum stroke 0 7 18 mm Opening time for maximum stroke 12 s Closing time 0 8 s Control signal Reference input signal Combustion air pressure Contro...

Страница 4: ... pressure acts on the regulator causing the air diaphragm to move to the left and close the regulating hydraulic bypass valve When the actuator is powered the gas valve begins to open The downstream differential gas pressure immediately begins to increase until the downstream gas pressure is in balance with the air pressure in accordance with the pressure ratio adjusted on the regulator The bypass...

Страница 5: ... SKP70 leakage due to diaphragm rupture stops when the burner shuts off and the valve is closed Conventional regulators continue to leak and therefore have to be vented to the outdoors N N N No o o ot t t te e e e To avoid oscillation do not oversize the VG valve See Technical Instruction No 155 512P25 F F F Fi i i ig g g gu u u ur r r re e e e 1 1 1 1 S S S SK K K KP P P P7 7 7 70 0 0 0 U U U U O...

Страница 6: ...c c ce e e e The pressure connection pipes should be as short as possible to allow the regulator to react to sudden changes The connection pipe for the combustion chamber pressure must be installed so that condensing flue gases cannot enter into the regulator but run back into the combustion chamber If necessary a water separator must be installed W W W WA A A AR R R RN N N NI I I IN N N NG G G G ...

Страница 7: ...oximately 90 of full capacity 3 Measure CO2 or O2 content in the flue gases and correct the ratio by adjusting screw until optimum values are obtained fine setting 4 Return to low fire and measure the CO2 or O2 content in the flue gases If necessary correct the setting by adjusting screw until optimum values are obtained 5 Limit the damper position for low fire operation If considerable parallel d...

Страница 8: ... Fi Fi Fitt tt tt tti i i in n n ng g g g A A A AG G G GA A A A78 78 78 78 F F F Fi i i ig g g gu u u ur r r re e e e 4 4 4 4 A A A AG G G GA A A A7 7 7 78 8 8 8 O O O Op p p pe e e er r r ra a a at t t ti i i io o o on n n n F F F Fi i i ig g g gu u u ur r r re e e e 5 5 5 5 A A A AG G G GA A A A7 7 7 78 8 8 8 A A A Ad d d dj j j ju u u us s s st t t tm m m me e e en n n nt t t ts s s s Function ...

Страница 9: ... d di ii ing ng ng ng T T T Te e e ec c c chn hn hn hno o o ol ll log og og ogi ii ie e e es s s s I I I In n n nc c c c Landis Division 1000 Deerfield Parkway Buffalo Grove IL 60089 4513 USA Document No 155 516P25 Printed in the U S A P P P Pa a a age ge ge ge 9 9 9 9 o o o of f f f 9 9 9 9 D D D Di i i im m m me e e en n n ns s s si i i io o o on n n ns s s s F F F Fi i i ig g g gu u u ur r r re...

Отзывы: