background image

Document Number: 129-369 

Installation Instructions 

September 30, 2002 

Normally Closed Valve 

Actuator pressure cylinder moves:  

• 

Outward (0 to 1): Valve opens.  

• 

Inward (1 to 0): Valve closes. 

Normally Open Valve 

Actuator pressure cylinder moves: 

• 

Outward (0 to 1): Valve closes.  

• 

Inward (1 to 0): Valve opens. 

Three-Way Valve 

Actuator pressure cylinder moves: 

• 

Outward: Valve opens between port NC and C. 

• 

Inward: Valve opens between ports NO and C. 

NOTE: 

The valve body assembly determines the 
complete assembly action. 

Manual Operation 

EA1080R1

<< MAN >>

<< AUTO >>

<< AUTO >>

>3x360

1

0

 

0

1

0

0

1

0

1

0

1

0

1

EA0387R1

3/4 in.

(20mm)

Figure 11.  Manual Override in Manual 

 and Automatic Position. 

Each complete revolution (360°) is equal to 3/32-inch 
(2.5 mm) stroke. 

Reference 

Technical Instruction 

Document 

Number 

EA599-18 Flowrite 599 Series SKB/C/D 
62UA Series Electronic Valve Actuator, 24 
Vac Proportional Control Advanced Features 

155-717 

 

 

Figure 12.  Valve Stem Travel Indication. 

 

Dimensions  

8-13/16

(224)

11-1/4

(285)

2-9/16

(65)

1-15/16

(49)

4-1/2
(114)

3/4

(19)

4-13/16

(122)

4-13/16

(122)

9-3/8
(232)

12-7/8

(327)

5

(126)

EA0854R1

 

Figure 13.  599-10071 Weather Shield  

Dimensions in Inches (Millimeters).  

 

 
 
 

Siemens Building Technologies, Inc. 

Page 5 of 6 

Содержание SKD62UA

Страница 1: ...m hex wrench Small and medium flat blade screwdrivers Expected Installation Time 20 minutes for factory installed actuator 45 minutes for field replacement of actuator Prerequisites WARNING If mounting the actuator to a valve already in line either close the shut off valves in the piping upstream first then downstream or switch off the pump to allow the differential and static pressure in the valv...

Страница 2: ...th Mounting an Actuator to a Valve EA0134R1 Figure 3 Preparing a new Valve Mounting an Actuator to a Valve NOTE Install the packing heating element P N 599 00417 if used before proceeding EA0380R1 5 mm 3x360 5 x 360 MAN MAN Figure 4 NOTE Make sure the yoke nuts are loose enough to allow the actuator to slip over the bonnet See Figure 5 EA0382R1 4 3 Figure 5 EA0384R1 5 mm 5 Figure 6 NOTE Hold the s...

Страница 3: ...ring Diagrams EA1077R1 LED Status Indication Stroke Calibration Rotary Switches LO and UP Connection Terminals G0 AC 24V 50 60Hz 0 10V 4 20mA G G0 Chm G Y M U Z OK Green Status Calib Red Calib Error Valve Jam 1 2 3 4 Figure 9 DIP Switches DIP Switches From Left to Right 1 Select Direction of Operation 2 Sequence Control or Stroke Limit Control 3 Selection of Control Signal 4 Selection of Flow Char...

Страница 4: ...ecessary To initiate the calibration procedure short circuit the contacts inside the slot located on the printed circuit board with a screwdriver Automatic calibration proceeds as follows Actuator runs to the 0 stroke position 1 the green LED flashes Actuator then runs to the 100 stroke position 2 the green LED flashes 0 1 2 3 y 100 Stroke EA1066R1 Measured values are stored in the EPROM The actua...

Страница 5: ...tion Manual Operation EA1080R1 MAN AUTO AUTO 3x360 1 0 0 1 0 0 1 0 1 0 1 0 1 EA0387R1 3 4 in 20mm Figure 11 Manual Override in Manual and Automatic Position Each complete revolution 360 is equal to 3 32 inch 2 5 mm stroke Reference Technical Instruction Document Number EA599 18 Flowrite 599 Series SKB C D 62UA Series Electronic Valve Actuator 24 Vac Proportional Control Advanced Features 155 717 F...

Страница 6: ...13 16 300 4 3 4 120 0 1 0 1 1 0 EA0385R1 Information in this publication is based on current specifications The company reserves the right to make changes in specifications and models as design improvements are introduced Flowrite is a trademark of Siemens Building Technologies Inc Other product or company names mentioned herein may be the trademarks of their respective owners 2002 Siemens Buildin...