Document Number: 129-369 
Installation Instructions 
September 30, 2002 

Dimensions, Continued 

 

CAUTION: 

 

Use care when removing the knockout. Do 
not damage the circuit board.

 

NOTE: 

Use the top knockout position when installing the 
Weather Shield.  

 

SERVICE ENVELOPE 

 

MINIMUM ACCESS  

SPACE RECOMMENDED

 

 

 

4 inch (100 mm) 

 

 

 

8 inch (200 mm) 

 

Figure 14.  SKD62UA Dimensions in Inches (Millimeters). 

 

2-1/2

(64)

2-5/8

(66)

Ø2-9/16

(65)

Ø1-3/4

(44)

4-1/8
(105)

Ø5

(127)

5-5/8
(143)

KNOCKOUT

FOR STANDARD

1/2" CONDUIT

CONNECTOR

4-7/8
(123)

11-13/16

(300)

4-3/4
(120)

0

1

0

1

1

0

EA0385R1

 

Information in this publication is based on current specifications. The company reserves the right to make changes in specifications and models as 
design improvements are introduced. Flowrite is a trademark of Siemens Building Technologies, Inc.  Other product or company names mentioned 
herein may be the trademarks of their respective owners. © 2002 Siemens Building Technologies, Inc. 

 

Siemens Building Technologies, Inc. 

 

1000 Deerfield Parkway 

Your feedback is important to us. If you have 
comments about this document, please send 

Buffalo Grove, IL  60089-4513 
U.S.A. 

them to 

[email protected]

 

 

Page 6 of 6

 

Document No. 129-369. 

Printed in the U.S.A. 

Содержание SKD62UA

Страница 1: ...m hex wrench Small and medium flat blade screwdrivers Expected Installation Time 20 minutes for factory installed actuator 45 minutes for field replacement of actuator Prerequisites WARNING If mounting the actuator to a valve already in line either close the shut off valves in the piping upstream first then downstream or switch off the pump to allow the differential and static pressure in the valv...

Страница 2: ...th Mounting an Actuator to a Valve EA0134R1 Figure 3 Preparing a new Valve Mounting an Actuator to a Valve NOTE Install the packing heating element P N 599 00417 if used before proceeding EA0380R1 5 mm 3x360 5 x 360 MAN MAN Figure 4 NOTE Make sure the yoke nuts are loose enough to allow the actuator to slip over the bonnet See Figure 5 EA0382R1 4 3 Figure 5 EA0384R1 5 mm 5 Figure 6 NOTE Hold the s...

Страница 3: ...ring Diagrams EA1077R1 LED Status Indication Stroke Calibration Rotary Switches LO and UP Connection Terminals G0 AC 24V 50 60Hz 0 10V 4 20mA G G0 Chm G Y M U Z OK Green Status Calib Red Calib Error Valve Jam 1 2 3 4 Figure 9 DIP Switches DIP Switches From Left to Right 1 Select Direction of Operation 2 Sequence Control or Stroke Limit Control 3 Selection of Control Signal 4 Selection of Flow Char...

Страница 4: ...ecessary To initiate the calibration procedure short circuit the contacts inside the slot located on the printed circuit board with a screwdriver Automatic calibration proceeds as follows Actuator runs to the 0 stroke position 1 the green LED flashes Actuator then runs to the 100 stroke position 2 the green LED flashes 0 1 2 3 y 100 Stroke EA1066R1 Measured values are stored in the EPROM The actua...

Страница 5: ...tion Manual Operation EA1080R1 MAN AUTO AUTO 3x360 1 0 0 1 0 0 1 0 1 0 1 0 1 EA0387R1 3 4 in 20mm Figure 11 Manual Override in Manual and Automatic Position Each complete revolution 360 is equal to 3 32 inch 2 5 mm stroke Reference Technical Instruction Document Number EA599 18 Flowrite 599 Series SKB C D 62UA Series Electronic Valve Actuator 24 Vac Proportional Control Advanced Features 155 717 F...

Страница 6: ...13 16 300 4 3 4 120 0 1 0 1 1 0 EA0385R1 Information in this publication is based on current specifications The company reserves the right to make changes in specifications and models as design improvements are introduced Flowrite is a trademark of Siemens Building Technologies Inc Other product or company names mentioned herein may be the trademarks of their respective owners 2002 Siemens Buildin...

Отзывы: