4. Switch on the power supply.
Switching on the supply voltage (Page 57)
5. Wait for 2 seconds.
After this start-up time, the device is operational.
6. Wait 5 minutes to get exact measured values.
5.5
Commissioning SITRANS TF with HART
Introduction
In this section, you will learn how to commission the device step-by-step.
Before you start, please read the following safety notes:
● General safety notes (Page 15)
● Basic safety notes: Installing/mounting (Page 19)
● Basic safety notes: Connecting (Page 31)
● Basic safety notes: Commissioning (Page 53)
Read the entire device manual in order to achieve the optimum performance of the device.
Procedure
1. Mount the device.
Mounting the SITRANS TF single chamber housing (Page 25)
Mounting the SITRANS TF dual chamber housing (Page 26)
2. Connect the device.
Connecting the SITRANS TF single chamber housing (Page 45)
Mounting the SITRANS TF dual chamber housing (Page 26)
3. Switch on the power supply.
Switching on the supply voltage (Page 57)
4. Wait for 2 seconds.
After this start-up time, the device is operational.
5. Wait 5 minutes to get exact measured values.
6. If you want to change the factory settings, configure the device using remote operation.
– Read the operating instructions for information on this.