Operation
5.11 Measure temperature
SITRANS TF280 WirelessHART
66
Operating Instructions, 10/2010, A5E02619566-02
5.11
Measure temperature
Requirement
You are acquainted with the principles of operation: Use of local user interface (Page 38)
Procedure
1.
Select unit.
Parameter: "2.3.1 Unit" (Page 48)
2.
Set the sensor pin connections.
Parameter: "2.3.5 Connections settings" (Page 49)
3.
Sensor calibration: Set value for lower adjustment (optional).
Parameter: "2.3.2 Lower adjustment" (Page 48)
4.
Sensor calibration: Set value for upper adjustment (optional).
Setting option only displayed following change to "Lower adjustment".
Parameter: "2.3.3 Upper adjustment" (Page 48)
5.
Reset sensor calibration. Then repeat steps 3 or 3 and 4 as necessary.
Parameter: "2.3.4 Reset adjustment" (Page 49)