Operation
5.6 Parameter descriptions
SITRANS TF280 WirelessHART
Operating Instructions, 10/2010, A5E02619566-02
49
"2.3.4 Reset adjustment"
Requirement:
The following parameter settings have been changed:
"2.3.2 Lower adjustment" (Page 48)
"2.3.3 Upper adjustment" (Page 48)
Factory setting:
START
Setting range:
-.
Purpose:
Reestablishment of factory calibration: Current temp. = setpoint temp.
Description:
Start function by pressing the M key.
Following resetting, the menu entry "Upper adjustment" is no longer
displayed.
"2.3.5 Connections settings"
Requirement:
The sensor is wired up: Connection of temperature sensor (Page 26)
Factory setting:
2-wire
Setting range:
2-wire
3-wire
4-wire
Purpose:
Define sensor connection.
Description:
Select the desired connection version by pressing the ↑ or ↓ key.
Accept the setting by pressing the M key.