Safety, approvals, EMC
7.2 Test voltage
SITOP PSU6200 1ph
62
Manual, 03.2019, A5E44623264-1-76
7.2
Test voltage
Figure 7-1
Test voltage diagram
Only the manufacturer can perform the type test and production test; users can also perform
the field test.
Preconditions for performing the field test:
Tests (A) & (B)
●
Connect the input terminals with one another (L1, N (L2))
●
Connect the output terminals, signaling contact and PE with one another
Test (C)
●
Connect the output terminals and signaling contact with one another and measure with
respect to PE
Table 7- 1
Test voltage
Test time
Prim ↔ sec (A)
Prim ↔ PE
(B)
Sec ↔ PE (C)
Type test
60 s
4200 V DC
2200 V DC
850 V DC
Production test
1 s
4200 V DC
2200 V DC
850 V DC
Field test
1 s
4200 V DC
2200 V DC
850 V DC
Remark:
Tripping current for DC measurement: max. 10 mA