2.5 Operating mode
SITOP PSU6200 1ph
Manual, 03.2019, A5E44623264-1-76
15
2.5
Operating mode
The selection is made using individual DIP switches (when supplied, these are in the 0
position).
It is only permissible to connect two identical devices in parallel to increase the power by
changing over the output characteristic by switching selector switch PO
⑪
to 1
DIP switch
6EP3324-7SB00-3AX0 (12 V/12 A)
6EP3334-7SB00-3AX0 (24 V/10 A)
6EP3336-7SB00-3AX0 (24 V/20 A)
COM ⑨:
Selector switch to toggle between the U
out
status display and the communication
0: Display of the output voltage status
1: Internal device parameters are transferred via signaling contact (13, 14) (diagnostics interface)
CAUTION: It is not permissible that the signaling contact is connected on the primary side!
Contact rating: 24 V AC/0.1 A; 30 V DC/0.1 A
HV ⑩:
Setting, above which value, the "O.K." LED is lit.
0: > 10 V
1: > 11.8 V
Setting, above which the "O.K." LED is lit
0: > 20 V
1: > 23 V
PO ⑪:
Switching over output characteristic 0: Constant output voltage "single operation" 1: Load-de-
pendent output voltage "parallel operation"
Additional information can be found in the documents:
●
Diagnostics interface (
https://support.industry.siemens.com/cs/ww/en/view/109763467
●
Faceplates and communication blocks
https://support.industry.siemens.com/cs/ww/en/view/109760217
Содержание SITOP PSU6200
Страница 8: ...Notes on safety SITOP PSU6200 1ph 8 Manual 03 2019 A5E44623264 1 76 ...
Страница 22: ...Mounting removal SITOP PSU6200 1ph 22 Manual 03 2019 A5E44623264 1 76 ...
Страница 42: ...Installation 5 2 Output side connection SITOP PSU6200 1ph 42 Manual 03 2019 A5E44623264 1 76 ...
Страница 74: ...Environment SITOP PSU6200 1ph 74 Manual 03 2019 A5E44623264 1 76 ...