Technical data
6.2 Output
SITOP PSU300S
Manual, 12.2016, C98130-A7587-A1-7-7629
37
6EP1433-2BA20
(24 V/5 A)
6EP1434-2BA20
(24 V/10 A)
6EP1436-2BA10
(24 V/20 A)
6EP1437-2BA20
(24 V/40 A)
Response when
switching on/off
Overshoot,
1.05 × U
out rated
Overshoot,
1.05 × U
out rated
No overshoot of U
out
(soft start)
Starting delay, max.
1.5 s
1.5 s
1.5 s
1.5 s
Voltage rise, typ.
60 ms
50 ms
30 ms
15 ms
Voltage rise time / of
the output voltage /
maximum
500 ms
500 ms
500 ms
500 ms
Rated current I
out rated
5 A
10 A
20 A
40 A
Current range
•
Remark
0 - 5 A
6 A to 45 °C
60 ... 70 °C derating:
5 % I
out rated
/K
0 - 10 A
12 A to 45 °C
60 ... 70 °C derating:
5 % I
out rated
/K
0 - 20 A
24 A to 45 °C
60 ... 70 °C derating:
2 % I
out rated
/K
0 - 40 A
48 A to 45 °C
60 ... 70 °C derating:
3 % I
out rated
/K
Output active power /
typical
120 W
240 W
480 W
960 W
Short-time overload
current / for a short
circuit when powering
up / typical
-
-
35 A
65 A
Duration of the over-
load capability, over-
current / for a short
circuit while powering
up
-
-
100 ms
100 ms
Short-time overload
current / for a short
circuit in operation /
typical
-
-
35 A
65 A
Duration of the over-
load capability, over-
current / for a short
circuit in operation
•
Remark
-
-
100 ms
every 2.5 s
100 ms
every 2.5 s
Can be connected in
parallel to increase the
power rating
Yes
Number of devices
that can be connected
in parallel to increase
the power rating, units
2
Overload capability
(Extra Power)
7.5 A for 5 s/min
15 A for 5 s/min
30 A for 5 s/min
60 A for 5 s/min
Output characteristic
(Page 38)
(Page 38)
(Page 39)
(Page 39)
Содержание SITOP PSU300S
Страница 8: ...Safety instructions SITOP PSU300S 8 Manual 12 2016 C98130 A7587 A1 7 7629 ...
Страница 34: ...Installation 5 2 Output side connection SITOP PSU300S 34 Manual 12 2016 C98130 A7587 A1 7 7629 ...
Страница 46: ...Technical data 6 9 Dimension drawing SITOP PSU300S 46 Manual 12 2016 C98130 A7587 A1 7 7629 ...
Страница 64: ...Environment SITOP PSU300S 64 Manual 12 2016 C98130 A7587 A1 7 7629 ...