Mounting position, mounting clearances
4
4.1
Standard mounting position
The device is mounted on standard mounting rails. The device must be mounted vertically in
such a way that the input terminals and the output terminals are at the bottom to ensure
correct cooling.
A clearance of at least 50 mm (6EP1433-2BA20 and 6EP1434-2BA20) – or 40 mm
(6EP1436-2BA10 and 6EP1437-2BA20), must be maintained above and below the device
(maximum depth of the cable duct, 50 mm).
No space is required at the side.
Output current as a function of the ambient temperature and mounting height
Figure 4-1
6EP1433-2BA20: Output current in the standard mounting position
Figure 4-2
6EP1434-2BA20: Output current in the standard mounting position