![Siemens SIPROTEC PROFINET IO Скачать руководство пользователя страница 73](http://html.mh-extra.com/html/siemens/siprotec-profinet-io/siprotec-profinet-io_manual_1265444073.webp)
3 Parameterization
3.2 Parameterization with DIGSI
73
SIPROTEC 4, Communication Module PROFINET IO, Communication Profile
C53000-L1840-C360-1, Edition 08.2012
The
System Configurator
opens with the
IEC61850 station
application.
−
Drag and drop the
NTP server
entered under
New devices (1)
into the
Subnet1
folder.
Figure 3-25 Integrating the NTP Server in Subnet1
−
Click
NTP server
and enter the
IP address
under
Parameter
in the
Properties
window (right
window). Change the
subnet mask
and the
standard gateway
, if necessary.
−
Close the
System Configurator
and confirm saving of the IEC 61850 station settings with
OK
.
✧
In DIGSI Manager, right-click the
IEC61850 station
and select the
Object properties...
entry in the menu.
✧
In the
Properties - IEC61850 station
dialog, select the
Update
tab and update the parameter set using
the
Update all parameter sets
button.
✧
Close the
Report
window.
Parameterizing the Device Functions
✧
Open the SIPROTEC device from the DIGSI user interface.
✧
Enter all desired settings in the DIGSI user interface (see Figure 3-12)..
✧
Save the parameter set and then close the device on the DIGSI user interface.
NOTE
The DIGSI manual describes these settings, e.g. protection settings, CFC charts and routings to binary inputs/
outputs or LEDs.
com_profinet-io_profile_us.book Page 73 Friday, August 17, 2012 1:40 PM