3 Parameterization
3.2 Parameterization with DIGSI
69
SIPROTEC 4, Communication Module PROFINET IO, Communication Profile
C53000-L1840-C360-1, Edition 08.2012
Changing an Existing Routing
If you want to assign an information item that is already routed to the system interface to a different (free)
PROFINET IO telegram position, select the
Object properties
dialog (see Figure 3-18) by selecting the
context menu item
Properties...
(right-click the line pertaining to the information in the
Display text
,
Long text
or
Type
column of the DIGSI Configuration Matrix).
Figure 3-19
Changing an Existing Routing
Depending on the information type in the
Object properties
dialog, select the following parameters in the
Protocol info source F
,
Protocol info destination B
or
Measured value destination B
tabs.
Protocol Information Source
Protocol Information Destination
Measurement Destination
Decision whether the measured value is transmitted as percentage value, primary value or secondary value.
Not all 3 options are available for each measured value.
NOTE
A port other than port B (for example port F) may be displayed as the
source
and
destination
of the system
interface (device-dependent).
Table 3-3
Protocol Information Source
Parameter
Information types
Remark
PROFINET IO mapping data-object number
IntSP, IntDP, C_XX, CF_XX
See Chapter 2.5
Table 3-4
Protocol Information Destination
Parameter
Information types
Remark
PROFINET IO mapping data-object number
SP, DP, OUT, IntSP, IntDP,
MV, PMV, MVMV, VI
See Chapter 2.5
com_profinet-io_profile_us.book Page 69 Friday, August 17, 2012 1:40 PM