3 Parameterization
3.1 Configuration of EN100 Network Parameters
56
SIPROTEC 4, Communication Module PROFINET IO, Communication Profile
C53000-L1840-C360-1, Edition 08.2012
3.1
Configuration of EN100 Network Parameters
Ethernet-Network Settings
The EN100 requires the following Ethernet network parameters for IP-based applications:
•
IP address
•
Subnet mask
•
Default gateway
There are 3 options for setting the parameters:
1. The network parameters are assigned when parameterizing the device using DIGSI and the IEC 61850
system configurator.
2. A commissioning tool (e.g. "Primary Setup Tool", see Chapter 3.4.1) is used to assign the network
parameters via DCP.
3. The IO controller assigns the network parameters to the respective addressed IO device (also via DCP)
when the PROFINET IO communication is launched.
Chapter 3.4.2 describes how to reset the network parameters to the factory settings via DCP. The EN100 is
restarted in the process.
If the network parameters specified via the IEC 61850 system configurator are to be set again after having
changed the network settings, either the device is to be loaded/initialized again via DIGSI or the network
parameters are to be set via DCP.
IO Device Name
The station name for the IO controller to identify the device is another basic setting for the EN100
(PROFINET IO device).
The device names for IEC 61850 (IED name) and PROFINET IO (station name) can be different. The device
name for IEC 61850 is assigned in the station configurator. The device name for PROFINET IO is assigned via
DCP, see Chapter 3.4.1.
A parameterized station name is permanently stored in the EEPROM of the EN100.
The set station name of the SIPROTEC device is displayed on the HTML page of the PROFINET IO diagnosis
(see Chapter 4.1).
NOTE
The network setting specified in the IEC 61850 station configurator is activated in the EN100 each time the
device parameters and EN100 parameters are loaded or initialized via DIGSI.
Changing the network settings via DCP is possible anytime afterwards. The new network parameters are
permanently stored and used in the EEPROM of the EN100. Restarting the SIPROTEC device or EN100 is not
necessary and is not automatically executed.
NOTE
A change to the network settings via DCP affects all IP applications running on the EN100, for example HTTP
server and IEC 61850 server. See also Chapter 3.4.1.
NOTE
EN100 with PROFINET IO does not support DHCP.
com_profinet-io_profile_us.book Page 56 Friday, August 17, 2012 1:40 PM