Appendix
A-11
7SS60 Manual
E50417-G1176-C132-A2
A.5
Jumper settings for the peripheral modules
Restraint/
command output
module 7TM700
Figure A-6
Location of the jumpers on the 7TM700 restraint/command output module (delivery status)
220/250V
110/125V
48/60V
X21
4
3
2
1
220/250V
110/125V
48/60V
X22
4
3
2
1
220/250V
110/125V
48/60V
X23
4
3
2
1
220/250V
110/125V
48/60V
X24
4
3
2
1
220/250V
110/125V
48/60V
X25
4
3
2
1
X1
X2
Jumper
Rated auxiliary voltage
24 / 48 Vdc
110 / 125 Vdc
220 / 250 Vdc
X21
1–2
2–3
3–4
X22
1–2
2–3
3–4
X23
1–2
2–3
3–4
X24
1–2
2–3
3–4
X25
1–2
2–3
3–4