Technical Data
9-8
7SS60 Manual
E50417–G1176–C132–A2
9.1.4
Matching transformers
Thermal overload
capability
max. thermal overload capability for all 2 transformer types under simultaneous load
of all turns
for 10 s
8 x I
N
for 1 s
20 x I
N
Weight
approx. 3.7 kg
4AM5120-1DA00-0AN2
for connection to current
transformers with a
rated current I
N
of
1 A
Rated frequency f
N
45-60 Hz
Winding
Number of turns
A-B
1
B-C
2
D-E
4
E-F
8
G-H
16
H-J
32
Y-Z
500
Max. current, continuous
A
6.8
6.8
6.8
6.8
6.8
6.8
0.85
Max. voltage
V
0.4
0.8
1.6
3.2
6.4
12.8
200
4AM5120-2DA00-0AN2
for connection to current
transformers with a
rated current I
N
of
5 A
Rated frequency f
N
45-60 Hz
Winding
Number of turns
A-B
1
B-C
2
D-E
4
E-F
8
Y-Z
500
Max. current, continuous
A
26
26
26
26
0,85
Max. voltage
V
0.4
0.8
1.6
3.2
200