Technical Data
9-6
7SS60 Manual
E50417–G1176–C132–A2
9.1.2.2
7TR710 isolator replica module/preferential treatment module
Isolator replica
Number of feeders
1
(single busbar and double busbar)
Number of isolators
2
(per 1 auxiliary contact) per feeder
Preferential
treatment
Number of preferential treatment circuits 2
Number of contacts per pref. treatm.
3 changeover contacts
Switching time
< 20 ms
Number of auxiliary relays
1
Contacts of auxiliary relay
2 changeover contacts
Auxiliary voltage
Rated auxiliary voltage U
H
48/60 Vdc
(38 to 72 Vdc)
(permissible voltage range)
110/125 Vdc
(88 to 150 Vdc)
220/250 Vdc
(176 to 300 Vdc)
depending on the ordering number,
see Chapter A.1
Power
consumption
Relay
Rated aux. voltage
max. power consumption, continuous
K1/K2, K3/K4
48 V
1.5 W
60 V
1.9 W
110 V
1.8 W
125 V
2.1 W
220 V
1.8 W
250 V
2.1 W
K5
48 V
0.4 W
60 V
0.5 W
110 V
0.5 W
125 V
0.6 W
220 V
1.1 W
250 V
1.2 W
Relay contacts
Switching capacity
MAKE
1000 W/VA
BREAK
30 W/VA
Switching voltage
250 V ac/dc
Permissible current
continuous
5 A
0.5 s
10 A
Weight
approx. 0.6 kg
Note:
The functions isolator replica or preferential treatment are alternatively available.
Содержание SIPROTEC 7SS60
Страница 1: ...E50417 G1176 C132 A2 SIEMENS SIPROTEC 7SS60 V3 1 Centralized Numerical Busbar Protection ...
Страница 2: ......
Страница 4: ...Siemens Aktiengesellschaft Document No E50417 G1176 C132 A2 ...
Страница 8: ...Preface iv 7SS60 Manual E50417 G1176 C132 A2 ...
Страница 50: ...Configuration 4 16 7SS60 Manual E50417 G1176 C132 A2 ...
Страница 80: ...Control in Operation 6 8 7SS60 Manual E50417 G1176 C132 A2 ...
Страница 112: ...Technical Data 9 18 7SS60 Manual E50417 G1176 C132 A2 ...