Functions
6-17
7SJ63 Manual
C53000-G1140-C120-1
•
Because the thermal cure of the overload protection is “frozen” (held constant) dur-
ing motor start-up, the setting must be high enough to allow operation of the over-
load protection at higher load current levels.
6.1.3.1
Settings
In the list below, the setting ranges and default setting values are for a device with a
nominal current rating I
N
= 5 A. Consider the current transformer ratios when setting
the device with primary values
For a nominal current rating I
N
= 1 A:
−
For the pickup current (I MOTOR START) , divide the Setting Options values and
default setting values by 5.
−
For the Ground resistance and reactance ratios, multiply Setting Range and Setting
Increments by 5!
1
) depending of the ordering code
6.1.3.2
Information
Addr.
Setting
Setting Options
Default Setting
Comments
1101
V PRIMARY OP.
0.10 ~ 400.00 kV
12.00 kV
Nominal operating voltage of primary
equipment
1102
I PRIMARY OP.
10 ~ 50,000 A
100 A
Nominal operating current of primary
equipment
1103
RG/RL Ratio
0.33 ~ 7.00
1.00
Ground resistance ratio
1104
XG/XL Ratio
0.33 ~ 7.00
1.00
Ground reactance ratio
1105
x’
0.002 ~ 2.000
Ω
/mile
1
)
0.200
Ω
/mile
1
)
Line reactance value in secondary
ohms
1106 x’
0.001 ~ 1.243
Ω
/km
1
)
0.124
Ω
/km
1
)
Line reactance value in secondary
ohms
1107
I MOTOR START
3.00 ~ 50.00 A
12.50 A
1
)
Motor start-up current
F#
LCD-Text
Comment
533
IA =
Primary interrupted current Phase A
534
IB =
Primary interrupted current Phase B
535
IC =
Primary interrupted current Phase C
501
Device Pickup
Pickup (protection)
511
Device Trip
device trip (general)
126
Prot ON/OFF
Protection On/Off (IEC60870-5-103)
561
Man.Clos.Detect
Manual Close Detection (Impulse)
356
> Manual Close
Manual Close
2720
> Enable ANSI#-2
> Enable 50/67-(N)-2 (override 79 blk)
4601
> 52-a
contact is open if breaker is open
4602
> 52-b
contact is open if breaker is closed
www
. ElectricalPartManuals
. com
Содержание siprotec 7SJ63
Страница 16: ...xiv 7SJ63 Instruction Manual C53000 G1140 C120 1 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 28: ...Introduction 1 12 7SJ63 Manual C53000 G1140 C120 1 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 112: ...SIPROTEC 4 Devices 4 38 7SJ63 Manual C53000 G1140 C120 1 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 346: ...Functions 6 182 7SJ63 Manual C53000 G1140 C120 1 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 494: ...Technical Data 10 48 7SJ63 Manual C53000 G1140 C120 1 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 604: ...Index Index 6 7SJ63 Instruction Manual C53000 G1140 C120 1 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...