4 Technical Data
128
6MD665 Manual
C53000-G1876-C103-3
4.1
General Device Data
4.1.1
Analogue inputs (optional)
Current inputs
Voltage inputs
Measuring trans-
ducer inputs
Limit range behav-
iour, current
Limit range behav-
iour, voltage
Rated system frequency
f
Nom
50 Hz or 60 Hz
(adjustable)
Rated current
I
Nom
1 A or 5 A
Burden per phase and ground path
– at I
Nom
= 1 A
Approx. 0.05 VA
– at I
Nom
= 5 A
Approx. 0.3 VA
Current overload capability
– Thermal (rms)
200 A for 1 s
15 A for 10 s
12 A continuous
– Dynamic (peak value)
250 I
Nom
(half-cycle)
Precision
≤
0.5 % of measured value at 50 % to 120 % I
Nom(under
reference conditions)
Secondary nominal voltage
80 V to 125 V
Measuring range
0 V to 170 V
Burden at 100 V
Approx. 0.3 VA
Voltage overload capacity
– Thermal (rms)
230 V continuous
Precision
≤
0.5 % of measured value at 50 % to 120 % V
Nom (under
reference conditions)
Input current
-20 mA DC to +20 mA DC
Overload capability
±
100 mA continuous
Input resistance
10
Ω
Power input
5.8 mW at 24 mA
Precision
< 1 % from rated value
(under reference conditions)
Overflow
Phase current > 1.2 x rated current
The derived quantities P, Q, S, cos
Φ
, sin
Φ
and
Φ
also
overflow as a result.
Overflow
Secondary input voltage at the device > 120 V
eff
The derived quantities P, Q, S, cos
Φ
, sin
Φ
and
Φ
also
overflow as a result.
Содержание SIPROTEC 6MD665
Страница 8: ...Preface vi 6MD665 Manual C53000 G1876 C103 3 ...
Страница 14: ...Contents vi 6MD665 Manual C53000 G1876 C103 3 ...
Страница 140: ...3 Installation and Commissioning 126 6MD665 Manual C53000 G1876 C103 3 ...
Страница 166: ...4 Technical Data 152 6MD665 Manual C53000 G1876 C103 3 ...
Страница 201: ...A 9 Group Alarms 187 6MD665 Manual C53000 G1876 C103 3 A 9 Group Alarms No Description No Description ...
Страница 210: ...Literature 196 6MD665 Manual C53000 G1876 C103 3 ...
Страница 222: ...Index 208 6MD665 Manual C53000 G1876 C103 3 ...