Functional description
I IA CE
SIPLUS RIC IEC on S7 V1.5
Page 11 of 28
©SIEMENS AG 2013
3.1.1.1. Nodal block MAoSLi_MD_pDB (FB161)
The bl
ock has to be embedded between ‚SL_ORG_ASDU’ of the target application (Slave) and
‚S7_IEC_Config’ of the source application (Master).
The block transfers the information received by telecontrol messages from the Master connection to the
Slave connection.
In the simplest case it is carried out “transparent” i.e. the information are transferred 1
to 1 without any pre-processing.
CALL "MAoSLi_MD_pDB" , DB261
Comp_ID :=
Para_Image_DB :=162
max_No_of_Images :=
P_Application_Src :=#P_Appl_MA
ASDU_Adr_Src :=L#111
First_Info_Adr_Src :=L#1
Last_Info_Adr_Src :=L#20000
Filt_15_13_11_9_7_5_3_1 :=
P_SLi :=#P_Sli_Sl
Tx_Prio_L :=
Tx_Prio_H :=
PrioH_15_13_11_9_7_5_3_1:=
wTime_15_13_11_9_7_5_3_1:=
Inro_QOI :=
IC_15_13_11_9_7_5_3_1 :=
TwoC_15_13_11_9_7_5_3_1 :=
Threshold_Val_ME :=1.001
FB_RetVal :=MW200
IM_DB_No :=MW202
No_used_IMs :=MW204
New_Image :=M206.0
Illustration as CFC-block with default values
Illustration in AWL with fractional parameter supply
Important features are:
With minor effort of parameterization
much information (‚max_No_of_Images’) can be pro-
cessed:
- Single indication with TK 1,2,30
- double indication with TK 3,4,31
- transformer tap with TK5,6,32
- Bit pattern with TK7,8,33
- measured value normalized value with TK9,10,34
- measured value with scaled value with TK11,12,35
- measured value with short floating point number
with TK13,14,36
- integrated totals with TK15,16,37
Readings for the default adjustments can be taken from the corresponding variable comment.
On the other hand only a minimum of mandatory inputs are required.
The interconnection of ‚P_Application_Src’, ‚ASDU_Adr_Src’ and ‚P_SLi’ is a minimum require-
ment.
automatic update of the image-DB with filter possibility for
-
defined address bands with ‚First_Info_Adr_Src’, ‚Last_Info_Adr_Src’
-
certain information types with ‚Filt_15_13_11_9_7_5_3_1’
Adjustable processing per information type
- Priority
- time stamp
- GI (in parallel to the general interrogation (GI) a group interrogation is supported)
- Transfer also without changes
Automatic designation of all information with status not topical (NT) in case of disturbed connec-
tion to the subordinated station.
Optional assignable parameter block for
- Individual quantity structure
- Address conversion (of the information object address)
- parameterizable threshold for measured values per information
- possibility of image access (diagnosis / further processing)