![Siemens SINAMICS PERFECT HARMONY GH150 6SL3826 Скачать руководство пользователя страница 77](http://html.mh-extra.com/html/siemens/sinamics-perfect-harmony-gh150-6sl3826/sinamics-perfect-harmony-gh150-6sl3826_operating-instructions-manual_378209077.webp)
See also
6.5
Connecting ground
DANGER
Danger to life as a result of insufficient grounding
The drive must be grounded to ensure that it operates safely and reliably. If the drive is
operated with insufficient grounding, then the protection and monitoring functions can fail.
Death, serious injury, or material damage will result.
● To ensure the correct functioning of the protection and monitoring equipment, ground the
device.
● To ensure the drive operates safely, connect a protective grounding conductor.
A shield busbar and a grounding lug can be found in the lower area of the cabinets.
Grounding bar and grounding lug are used for grounding the components installed in the
cabinet.
6.6
Laying the signal lines
Malfunction due to common cable installation
Malfunctions can occur in the converter if cables with differing voltage levels are laid together
with internal cables in one cable duct in the cabinet.
● Do not run cables coming from the outside, for example to the terminal strips, together with
internal cables in one cable duct.
Ensure that the following instructions are complied with:
● All signal lines must be shielded. The cable shield should be braided, because cables
shielded by tape or foil are five times less efficiently protected against interference. Always
ground the cable shields at both ends. Contacting at one end is advantageous in
exceptional cases only.
● Clamp the shield of incoming analog and binary cables to the shield busbar at the entry point
into the cabinet. Continue running the cable, still shielded, to the terminal strip or board. No
shields are connected to the terminal strips or boards.
Electrical connection
6.6 Laying the signal lines
SINAMICS PERFECT HARMONY GH150 6SL3826
Operating Instructions 05/2020
77
Содержание SINAMICS PERFECT HARMONY GH150 6SL3826
Страница 2: ...19 06 2020 09 25 V14 00 ...
Страница 120: ...Spare parts SINAMICS PERFECT HARMONY GH150 6SL3826 120 Operating Instructions 05 2020 ...
Страница 124: ...Service Support SINAMICS PERFECT HARMONY GH150 6SL3826 124 Operating Instructions 05 2020 ...
Страница 130: ...Quality documents SINAMICS PERFECT HARMONY GH150 6SL3826 130 Operating Instructions 05 2020 ...
Страница 132: ...Additional documents SINAMICS PERFECT HARMONY GH150 6SL3826 132 Operating Instructions 05 2020 ...
Страница 135: ......
Страница 136: ...Further Information www siemens com LDA Siemens AG Large Drives Applications Vogelweiherstr 1 15 90441 NÜRNBERG GERMANY ...