Note
Selecting replacement thyristors
Use only the approved thyristor types for the mounting location. Observe the equipment
installation log when replacing the thyristor.
DANGER
Danger when not complying with the five safety rules
Work must only be performed on adequately grounded power unit. Non-observance of the
five safety rules can cause death or serious injury. Serious material damage can also result.
• Observe the five safety rules.
You can replace thyristors within 5 minutes using simple tools. Plastic holders support the
thyristors against the heat sinks. The heat sinks are suspended on springs. A cup-spring
assembly produces the necessary clamping force in the stack.
Removing a thyristor
1. Insert the open-ended wrench
①
into the groove of the guide bolt
②
.
①
Open-ended wrench
②
Guide bolt
Figure 9-9
Open-ended wrench in groove
2. Keep the cup-spring assembly under tension with the open-ended wrench.
3. Use the socket wrench to loosen the clamping screw until the thyristors are resting loosely in
the plastic holders.
4. Pull the two gating leads off the thyristor.
5. Take the thyristor out.
Maintenance
9.6 Repairs
3rd Party LCI Control Upgrade
132
Operating Instructions, 02/2022, A5E31872818
Содержание SINAMICS MV 9LD4110-7EX70-1AA0
Страница 2: ......
Страница 60: ...Description 3 5 Options 3rd Party LCI Control Upgrade 58 Operating Instructions 02 2022 A5E31872818 ...
Страница 114: ...Operation 8 5 Fault and system messages 3rd Party LCI Control Upgrade 112 Operating Instructions 02 2022 A5E31872818 ...
Страница 140: ...Spare parts 3rd Party LCI Control Upgrade 138 Operating Instructions 02 2022 A5E31872818 ...
Страница 144: ...Service Support 3rd Party LCI Control Upgrade 142 Operating Instructions 02 2022 A5E31872818 ...
Страница 153: ......