Page 24
Version 1.0 March 1, 2000
1.3.3 Vector Control without Encoder Feedback
Note: Complete section 1.3.1 (Volts/Hz control without encoder feedback).
P060 = 5
P100 = 3
P060 = 1
P115 = 4
Wait
P060=5
Select “Drive Settings”
P100=3
Selects Vector Control
without Encoder Feedback
P060 = Return to Parameter Menu
If you plan to use an encoder, go to
section1.3.4, otherwise continue.
P115 = 4 No-Load Measurement
Uncoupled motor will ROTATE.
Alarm message “A080” will appear,
and a start command must be issued
within 20 seconds to perform the test,
otherwise P115 will unset.
This test will adjust the following
parameters
P103, P120
Wait for display to change back
to
o
009.
Содержание SIMOVERT MASTERDRIVES 6SE70 VC
Страница 4: ...Page 4 Version 1 0 March 1 2000 ...
Страница 6: ...Page 6 Version 1 0 March 1 2000 ...
Страница 16: ...Page 16 Version 1 0 March 1 2000 ...
Страница 28: ...Page 28 Version 1 0 March 1 2000 ...
Страница 30: ...Page 30 Version 1 0 March 1 2000 ...
Страница 32: ...Page 32 Version 1 0 March 1 2000 ...
Страница 34: ...Page 34 Version 1 0 March 1 2000 ...
Страница 40: ...Page 40 Version 1 0 March 1 2000 ...
Страница 44: ...Page 44 Version 1 0 March 1 2000 ...
Страница 48: ...Page 48 Version 1 0 March 1 2000 ...
Страница 56: ...Page 56 Version 1 0 March 1 2000 ...