Page 18
Version 1.0 March 1, 2000
P106 = ?
P107 = 60
P108 = xxxx
P115 = 1
P340 = 3
P383 = xxxx
P452 = 100
P106 = NEMA Motor Nameplated
efficiency (if unknown set =0.8)
P107 = Rated Motor Frequency
P108 = Nameplated Rotor RPM
P115 = 1
“Automatic Parameterization”
P340 = Carrier Frequency
Low # = Cooler Motor and Drive
High # = Lower Motor Noise
P383 = Motor Thermal Time
Constant. If constant unknown use
general guidelines;
2 Pole Motor = 480 seconds
4 Pole Motor = 600 seconds
6 Pole Motor = 720 seconds
P452 = Maximum Forward Speed in
Percentage (usually 100%)