11.98
Connection
Siemens AG 67087-6AC85-0AA0
ENGLISH
3-5
Common Rectifier Operating instructions
3.2.2
Signalling relay X36 ('Warning' signal)
Plug-in terminal X36
Terminals
Function description
perm. conductor
cross-section
(mm
2
)
(AWG)
X36-1
X36-2
Signalling contacts to switch extra-low voltage between terminals
1 and 2 at a switching voltage of DC 30 V max.DC 5 A, at a
switching voltage of AC 60 V max. AC 5 A at cos
ϕ
≥
0,4
0,2 to 2,5
24 to 14
Table 3.5
Warning
3.2.3
Settings on the module A23:
R2:
0 resistance as earth - reference potential M connection
On delivery, M is connected to earth. Remove this resistor only to avoid disturbances from earth loops, i.e. if the
electronic reference potential is otherwise connected to earth (e.g. via the reference potential connection
terminal of the power supply unit. The 0 resistor R210 on the A50 module must additionally be removed when
using the additional power suppy A50 (see Chapter 9.1).
S1:
Set the rated supply voltage with S1 (Piano DIP switch) (press down the applicable lever). Only one voltage
must be selected.
The setting of the system mains voltage on the switch S1 must correspond exactly with the one set on the
connected converters, thus guaranteeing a correct bypassing sequence and load current extraction (see
Chapter 4, Table 4.1 or 4.2).
S2:
The status of the bridging relays can be switched through to the "Warning" output (terminal X36) with S2
(DIP-Fix). When S2 is open, the "Warning" relay is opened only in the event of the excess temperature pre-
warning.
3.3
Control terminal strip of options
CAUTION
The unit must be in the deenergised state in order to connect the control lines to X9, X36
and X37.
♦
A50 additional power supply PSR for optional modules
Connector X37
Connector X37
Function description
Pin 1
DC 24V connected to terminal X9-1 via a 2A slow-blow fuse
Pin 2
Electronic reference potential connected to terminal X9-2 via a 3.2A slow-blow fuse
Table 3.6
Connection of additional power supply