11.98
Start-up
Siemens AG 6SE7087-6AC85-0AA0
ENGLISH
4-3
Common Rectifier Operating instructions
Rated voltage U
n
chained in V
rms
(A.C.)
Nominal dc link voltage values
U
nd
in V=
(set parameter P071 on the
SIMOVERT Master Drive)
On threshold
of U
d
in V=
Off threshold
of U
d
in V=
600 789
663 546
575 756
635 523
525 690
580 478
500 657
552 455
Table 4.2
On and off thresholds for units 6SE70xx-xFx8x
S1
Size B
S1
L1
460
440
415
400
380
230
L2
600
575
525
500
---
---
Size C
L1
460
440
415
400
380
230
L2
600
575
525
500
---
---
1 0
1
2
3
4
5
6
S1
S3
Position on A23
0 1
6
5
4
3
2
1
S1
S3
Position on A23
Fig. 4.1 Selector switches S1 and S3 on the A23 board 460 V position also for 480 V, S3 for 200 V
The following commissioning steps must be carried out after connecting the unit
(as detailed in Chapter 3):
♦
Set the rated mains voltage with S1 (Piano DIP switch) (press the corresponding lever of the switch towards
the module). It is only permissible to select one voltage (S3 also open).
The 200 V voltage range is activated by closing DIP-fix jumper S3 (by means of S1), whereby all the levers
of S1 must be open.
Works setting:
for 200-230V and 380-480V units = 400V
for 500-600V units = 500V
♦
The status of the bridging relays can be switched through to the "Warning" output (terminal X36) with the
jumper S2 (DIP-Fix). When S2 is open, the "Warning" relay is opened only in the event of the excess
temperature pre-warning.
Works setting:
S2 open
♦
Switch on the mains and electronic power supply.
♦
Enable the converter.
www
. ElectricalPartManuals
. com