4. When positioning the machine, ensure that a uniform axial gap (y→0) is maintained around
the coupling.
5. Fix the machine to the foundation. The choice of fixing elements depends on the foundation
and is the plant operator's responsibility.
'
[
\
①
Plates placed under the motor for alignment
②
Laser alignment
Figure 5-4
Schematic diagram: Aligning the machine to the driven machine
Table 5-2
Permissible deviations for aligning the machine with flexible coupling
Max. speed n
max
Max. parallel offset x
Max. angular offset y
n
max
≤ 1500 rpm
x
max
= 0.08 mm
y
max
= 0.08 mm / 100 mm ∅ D
1500 rpm <
n
max
≤ 3600 rpm
x
max
= 0.05 mm
y
max
= 0.05 mm / 100 mm ∅ D
Note
Machine expansion
When performing alignment, make allowance for the thermal expansion of the machine due to
rising temperature.
See also
Tightening torques for screw and bolt connections (Page 173)
Assembly
5.4 Installing the machine
SIMOTICS FD 1MQ1
Operating Instructions 01/2019
63
Содержание SIMOTICS FD 1MQ1
Страница 2: ...28 01 2019 14 14 V11 01 ...
Страница 48: ...Preparations for use 4 20 Converter operation SIMOTICS FD 1MQ1 48 Operating Instructions 01 2019 ...
Страница 108: ...Start up 7 11 Setting the motor parameters at the converter SIMOTICS FD 1MQ1 108 Operating Instructions 01 2019 ...
Страница 144: ...Maintenance 9 2 Corrective Maintenance SIMOTICS FD 1MQ1 144 Operating Instructions 01 2019 ...
Страница 166: ...Spare parts 10 19 Auxiliary terminal box 1XB302 SIMOTICS FD 1MQ1 166 Operating Instructions 01 2019 ...
Страница 170: ...Disposal 11 5 Disposal of components SIMOTICS FD 1MQ1 170 Operating Instructions 01 2019 ...
Страница 172: ...Service and Support SIMOTICS FD 1MQ1 172 Operating Instructions 01 2019 ...
Страница 176: ...Quality documents SIMOTICS FD 1MQ1 176 Operating Instructions 01 2019 ...
Страница 181: ......