5.3.9
Draining condensation
Under the following conditions it is possible that condensate may accumulate within the
machine:
● Wide fluctuations in the ambient temperature, such as direct sunshine combined with high
atmospheric humidity
● Intermittent operation or load fluctuations during operation
NOTICE
Damage due to condensate
If the stator winding is damp, its insulation resistance will be reduced. This can result in
voltage flashovers, which can destroy the winding. Condensate can also cause rust to form
within the machine.
Ensure that condensate can drain away.
Depending on the type of installation, the water drainage holes are located at the bottom:
Allow the condensation water to discharge for vertical placement
In the DE bearing shield, water drain holes are located in the area of the mounting feet or
opposite the regreasing system. They are sealed with screw plugs.
Figure 5-2
Condensation water drain for vertical mounting
Assembly
5.3 Lift the machine to where it will be installed, and position it
SIMOTICS FD 1MM1
62
Operating Instructions 02/2019
Содержание SIMOTICS FD 1MM1 Series
Страница 2: ...05 02 2019 16 03 V11 01 ...
Страница 30: ...Description SIMOTICS FD 1MM1 30 Operating Instructions 02 2019 ...
Страница 50: ...Preparations for use 4 19 Converter operation SIMOTICS FD 1MM1 50 Operating Instructions 02 2019 ...
Страница 94: ...Electrical connection 6 6 Connecting the auxiliary circuits SIMOTICS FD 1MM1 94 Operating Instructions 02 2019 ...
Страница 142: ...Maintenance 9 2 Corrective Maintenance SIMOTICS FD 1MM1 142 Operating Instructions 02 2019 ...
Страница 166: ...Disposal 11 5 Disposal of components SIMOTICS FD 1MM1 166 Operating Instructions 02 2019 ...
Страница 168: ...Service and Support SIMOTICS FD 1MM1 168 Operating Instructions 02 2019 ...
Страница 172: ...Quality documents SIMOTICS FD 1MM1 172 Operating Instructions 02 2019 ...
Страница 177: ......