4.19.3
Converter input voltage
The insulation system of SIMOTICS machines always complies with the requirements of stress
category C (IVIC C = high stress). If voltage peaks higher than those specified according to
IVIC C can occur, then please contact your Siemens partner:
● For a line supply voltage (converter input voltage) up to max. 480 V, and when controlled
from a SINAMICS G/SINAMICS S converter with uncontrolled/controlled infeed: Comply
with the guidelines for configuring motor and converter.
● For line voltages (converter input voltages) higher than 480 V, motors, which are ordered for
converter operation, have an appropriate insulation system.
● Operation with a converter from another manufacturer: Comply with the permissible voltage
peaks according to IEC 60034-18-41 in accordance with stress category C, dependent on
the particular line voltage (converter input voltage) and the motor insulation system.
NOTICE
Material damage caused by an excessively high supply voltage
The insulation system will be damaged if the supply voltage is too high for the insulation
system. This can completely destroy the machine.
● Comply with the peak voltages as laid down in the guidelines above.
4.19.4
Reducing bearing currents
Taking the following actions will reduce the bearing currents:
● Ensure that the contacts are established over a large area. Solid copper cables are not
suitable for high frequency grounding because of the skin effect.
Equipotential bonding conductors:
Use equipotential bonding conductors:
● Between motor and driven machine
● Between motor and converter
● Between the terminal box and the RF grounding point at the motor enclosure.
Selecting and connecting the cable:
As far as possible, use symmetrically arranged, shielded connection cables. The cable
shielding, made up of as many strands as possible, must have good electrical conductivity.
Braided shields made of copper or aluminum are very suitable.
● The shield is connected at both ends, at the motor and converter.
● To ensure good discharging of high-frequency currents, provide contacting over a large
surface area:
– as contact established through 360° at the converter
– at the motor, for instance with EMC glands at the cable entries
Preparations for use
4.19 Converter operation
SIMOTICS FD 1MM1
46
Operating Instructions 02/2019
Содержание SIMOTICS FD 1MM1 Series
Страница 2: ...05 02 2019 16 03 V11 01 ...
Страница 30: ...Description SIMOTICS FD 1MM1 30 Operating Instructions 02 2019 ...
Страница 50: ...Preparations for use 4 19 Converter operation SIMOTICS FD 1MM1 50 Operating Instructions 02 2019 ...
Страница 94: ...Electrical connection 6 6 Connecting the auxiliary circuits SIMOTICS FD 1MM1 94 Operating Instructions 02 2019 ...
Страница 142: ...Maintenance 9 2 Corrective Maintenance SIMOTICS FD 1MM1 142 Operating Instructions 02 2019 ...
Страница 166: ...Disposal 11 5 Disposal of components SIMOTICS FD 1MM1 166 Operating Instructions 02 2019 ...
Страница 168: ...Service and Support SIMOTICS FD 1MM1 168 Operating Instructions 02 2019 ...
Страница 172: ...Quality documents SIMOTICS FD 1MM1 172 Operating Instructions 02 2019 ...
Страница 177: ......