● 1XB7740
– For 12 or fewer cables and lower cross-sections, you can rotate the terminal box with
installed stator cables through ±90°.
– For more than 12 cables - or for cables with a cross-section greater than 50 mm² - you
must remove the internal stator cables before rotating the terminal box.
● 1XB7750
– Remove the internal stator cables before rotating the terminal box.
Rotating a terminal box with mounted stator cables
1. Ensure that the motor is disconnected from the power supply.
2. Release two diagonally opposed screws for the cover, and secure the cover using two M10
threaded bars screwed in diagonally opposing one another. Release the two other screws
and lift the cover off the terminal box. The terminal box cover is very heavy. Especially when
in a lateral position, ensure that the terminal box does not fall down.
3. If the motor is already connected:
– Remove the cables of the power supply.
– Release the screw connection of the cable entry. Remove the cables through the
opening.
4. Remove the grounding straps on two sides of the terminal box lower section.
5. Remove the screwed joints of the lower section with the console or optionally the cable duct.
6. Screw in two eye-bolts diagonally in the M10 thread at the corners. Slightly raise the terminal
box housing using a crane.
7. Rotate the terminal box through ±90° in the desired direction. Carefully place the terminal
box down. Take care not to damage the seal.
8. Screw the terminal box with the console / cable duct (4 x M16, tightening torque 170 Nm).
9. Fasten the grounding straps to the terminal box lower section and the console or cable duct:
– After rotation, remove the plugs of the two nearest M8 threads on the console or cable
duct.
– Grind the surface at the drilled holes so that the grounding straps have metallic contact.
– Then fasten the two straps to the terminal box lower section and the console or cable
duct (4x M8, tightening torque 11 Nm).
– Protect the bare areas at the contact with corrosion protection.
10.Reconnect the power supply cables. More information:
– Connecting the grounding conductor (Page 83)
– Introducing and routing the cables ...
– Connecting cables ...
11.Screw in the two diagonally arranged threaded bars and slide the cover onto these bars.
Take care not to damage the seal.
12.Fix the two free screw connections and tighten by hand.
Electrical connection
6.3 Terminal box
SIMOTICS FD 1LH1
80
Operating Instructions 01/2019
Содержание SIMOTICS FD 1LH1
Страница 2: ...23 01 2019 19 26 V11 01 ...
Страница 28: ...Description SIMOTICS FD 1LH1 28 Operating Instructions 01 2019 ...
Страница 72: ...Assembly 5 5 Connecting the cooling water supply SIMOTICS FD 1LH1 72 Operating Instructions 01 2019 ...
Страница 122: ...Operation 8 10 faults SIMOTICS FD 1LH1 122 Operating Instructions 01 2019 ...
Страница 140: ...Maintenance 9 2 Corrective Maintenance SIMOTICS FD 1LH1 140 Operating Instructions 01 2019 ...
Страница 162: ...Disposal 11 5 Disposal of components SIMOTICS FD 1LH1 162 Operating Instructions 01 2019 ...
Страница 164: ...Service and Support SIMOTICS FD 1LH1 164 Operating Instructions 01 2019 ...
Страница 168: ...Quality documents SIMOTICS FD 1LH1 168 Operating Instructions 01 2019 ...
Страница 173: ......