Installation
2-24
SIMODRIVE base line A Start-Up
Filter
The line filter limits the cable-borne faults emitted from the drive
converter unit to permissible EMC values for industry.
Table 2-10 Technical specification (SIEMENS filter)
Designation Parameter Unit
Rated current
16
A
Power loss
20
W
Conductor cross
section
Max.4 mm
2
PE terminal
M6, stud
Weight
3.8
kg
Dimension
(WxHxD)
156x193x81 mm
System voltage
400/415
,
±
10
%,
3-phase AC
V
Degree of
protection
IP20
Humidity
classification
3K5, condensation and icing excluded
Permissible
ambient
temperature
●
Operation: -0 ~40,max.55 (with
derating)
●
Storage/transport: -25~70;
ºC
Installation
altitude
1000, 2000 (with derating)
m
Order No.:
6SN1111-0AA01-1BA0
Commutating
The commutating reactor is used to limit system disturbance or
reactor
instability, and store energy for step-up converter operation in
conjunction with infeed and regenerative feedback modules.
The commutating reactor is already integrated in the infeed module in
SIMODRIVE base line A. It is not required for customer to install another
commutating reactor.
Shielded plate
I
n order to meet the requirements of the EC Directive on EMC, the motor
cable should be shielded. The shielded plate is used to contact the shield
on shielded motor supply cables. The plates are provided with prepared
mounting points for brake connection terminals.
Please refer to Fig.2-13 and Fig.2-14 for mounting the plate in
SIMODRIVE base line A and wiring up the cables.