Installation
2-22
SIMODRIVE base line A Start-Up
Table 2-8 Required technical specifications *
Designation Parameter Unit
V1 (
6Nm, 11Nm, 8Nm, 16Nm
): 8.00
(customer tailored)
kVA
V2 (
3+3Nm, 3+6Nm, 3+8Nm, 6Nm+8Nm,
6+6Nm, 8+8Nm
): 8.00 (customer tailored)
kVA
Rated power
V1+V2 (8Nm +8Nm): 8.00 (standard)
kVA
Input voltage
3AC 380
V
Output voltage
3AC 380
V
Type
JBK3
Circuit voltage
UK
<8%
Terminal
protection class
IP20, Phoenix terminals are recommended
and with UL-approval
Voltage
endurance test
DC 2250V, 1 minute (type test)
V
Input current
without load
<10%
Vector degree
Y/Y0
Max. coil temp.
boost
<80 K
Remarks:
* It is valid for the tailored transformers, which is to be observed by the
customer when purchasing.