65
2.12
Connection Terminals
Terminals
Terminals for auxiliary supply, voltage inputs, current inputs,
binary outputs, I/O modules (optional):
Conductor cross section, rigid max.:
2.5 mm
2
Conductor cross section with ferrule:
1.5 mm
2
Stripping length:
9 mm
Tightening torque:
0.4 Nm to 0.5 Nm
RS485-Interface:
9-pole D-sub miniature female connector
Attention
Ground needs to be connected to
the SIMEAS P prior operation.