58
Dielectric test, routine test, 2 s
according to IEC 61010-1
Voltage inputs, binary outputs
AC: 2.2 kV
Current inputs
AC: 1.35 kV
Power supply
DC: 3.1 kV
Serial interface
AC: 500 V
Additional for I/O modules
Binary inputs and binary/relay
outputs to PG
AC: 2.2 kV
Analog inputs and analog outputs
to PG
AC: 500 V
Insulation type of inputs and outputs
Signal inputs (current)
Reinforced,
AC: max. 150 V, Cat III
Signal inputs (voltage)
Protective impedance,
AC: max. 600 V, Cat II or
AC: max. 300 V, Cat III
Power supply
Reinforced,
AC: max. 230 V,
DC: max. 250 V,
Cat II
Output contacts
Reinforced,
AC: max. 230 V,
DC: max. 250 V,
Cat II