Technical specifications
5.5 Climatic ambient conditions
Comfort Panels INOX PCT
Compact Operating Instructions, 05/2018, A5E38804191-AA
39
5.5.3
Operating Conditions
The following information applies to a device installed according to the specifications in these
operating instructions.
The HMI device is designed for weatherproof and stationary operation according to
IEC 60721.
The device meets the requirements according to IEC 60721-3-3 Class 3K3 with the following
amendments and limitations:
Type of condition
Mounting position
Permitted range
Temperature,
Mounting in horizontal format
Vertical
0 ... 50 °C
1
Inclined, maximum inclination 35° 0 ... 40 °C
Temperature,
Mounting in vertical format
Vertical
0 ... 40 °C
Inclined, maximum inclination 35° 0 ... 35 °C
High-pressure cleaner
temporarily 80 °C: clean 3 min. maximum with 80 °C hot water, then
let it cool down
Atmospheric pressure
2
, oper-
ation elevation
1140 ... 795 hPa, corresponds to an elevation of -1000 to 2000 m
Relative humidity
From 10 ... 90%, no condensation on the rear panel of the device
Pollutant concentration
SO2: < 0.5 ppm; relative humidity < 60%,
no condensation at the rear of the device
H
2
S: < 0.1 ppm; relative humidity < 60%,
no condensation at the rear of the device
1
TP1900 Comfort and TP2200 Comfort: 0 ... 45 °C
2
No pressure difference is allowed inside and outside the enclosure / control cabinet
Read the Notes on use (Page 14).
Also observe the climate diagram in the following section and the specifications for the
extended inclination and ambient temperature range; see section "Permitted mounting
Note
The system components connected to the HMI device, the power supply for example, must
also be suited to the respective operating conditions.