Installing the Module
2-13
High Speed Counter Encoder Module User Manual
2.5
Configuring I/O Addresses in the Controller
After installing the module in the I/O base, you must assign the I/O starting
address in your programmable controller (PLC) memory. (The module is not
automatically assigned an I/O address in the controller.)
NOTE:
Even though the module may appear to be operating correctly, it
does not communicate with the PLC unless it is configured in the I/O map.
To confirm the I/O map and verify controller-to-module communications,
connect a PLC programming device (e.g., TISOFT
t
) to the controller. (For
information on configuring the I/O, refer to your SIMATIC TI505 TISOFT2
User Manual.) Power up the base and follow these steps:
1.
Ensure that the
MOD GOOD
indicator is on and the error bit is clear.
2.
In TISOFT, access the Configure I/O function menu.
3.
Select the appropriate channel and base number.
4.
Execute the Read Base function.
The HSCE module appears as 18 WX inputs and 14 WY outputs. In the
example shown in Figure 2-11, the module is located in slot 1. It uses
32 I/O address locations.
5.
Assign the starting I/O address and write the completed I/O
configuration to the controller memory, using the Write PLC functions.
In the example for slot 1, the starting address is set for 0001.
I/O Module Definition for:
Channel 1 Base 00
I/O Address:
The HSCE module logs in as 18 WXs and 14 WYs.
I/O
Number of Bit and Word I/O Special
Slot
Address
X Y WX WY Function
01
0001
00 00 18 14 No
02
0033
16 00 00 00 No
03
0049
00 08 00 00 No
04
0000
00 00 00 00 No
Slot Number:
Install the module into any slot in the I/O base.
SF Module:
The HSCE module is not a
Special Function Module.
Base Number:
Displays number of
the current base.
Figure 2-11
Sample I/O Module Definition Chart