Troubleshooting
B-2
High Speed Counter Encoder Module User Manual
B.1
LED Status and Error Code Descriptions
Table B-1 presents the status indications of the module’s LEDs.
Table B-1
LED Indicator Status Chart
MOD GOOD
(Red)
RUN
(Green)
Description
Off
Off or On
No base power, or fatal error exists
On
On
Normal run condition
On
Off
Module not in Run mode
On
Fast blink
Module not programmed
Off
Slow double
blink
User power supply fault detected
Off
Slow single
blink
Module fault: hardware or software error detected;
power cycle module to attempt recovery.
Table B-2 lists the error codes reported to the PLC using the WX words.
These error codes overwrite the values in words WX1 through WX16. If
Error bit (WX18.03) is clear and Run bit (WX18.01) is set, then there are no
error codes in the I/O words.
Table B-2
Error Codes in I/O Words
Integer
Hex
Code
Error Bit
(WX18.03)
Run Bit
(WX18.01)
Description
32767
7FFF
0 or 1
0
Module failed
32766
7FFE
0 or 1
0
Module in Programming Mode
32765
7FFD
1
0
Error in programming
32764
7FFC
1
0
Module not programmed
32763
7FFB
1
0 or 1
Module software failed
32762
7FFA
–
–
Factory test mode
32761
7FF9
–
–
Reserved for future use
32760
7FF8
–
–
Reserved for future use
32759
7FF7
–
–
Reserved for future use
32758
7FF6
–
–
Reserved for future use
32757
7FF5
–
–
Reserved for future use
32756
7FF4
–
–
Reserved for future use
32755
7FF3
–
–
Reserved for future use
32754
7FF2
–
–
Reserved for future use
32753
7FF1
0 or 1
0
Output power failed
32752
7FF0
–
–
Reserved for future use
0
0000
Default (no data); module
overwrites with valid count data