B-9
SIMATIC TD 200 Operator Interface
C79000-G7076-C272-01
The following descriptions are an introduction to general isolation characteristics of
the S7-200 family, but some features may be different on specific products.
Consult your product specifications in the appropriate manual for information about
which circuits include isolation boundaries and the ratings of the boundaries.
Isolation boundaries rated less than 1,500 VAC are designed as functional isolation
only, and should not be depended on as safety boundaries.
Logic circuit reference is the same as DC sensor supply M.
Logic circuit reference is the same as the input power supply M on a CPU with
DC power supply.
CPU communication ports have the same reference as logic circuit.
Analog inputs and outputs are not isolated from logic circuit. Analog inputs are
full differential to provide low voltage common mode rejection.
Logic circuit is isolated from ground to 500 VAC.
DC digital inputs and outputs are isolated from logic circuit to 500 VAC.
DC digital I/O groups are isolated from each other by 500 VAC.
Relay outputs are isolated from logic circuit to 1,500 VAC.
Relay output groups are isolated from each other by 1,500 VAC.
AC power supply line and neutral are isolated from ground, the logic circuit, and
all I/O to 1,500 VAC.
Multiple CPU Configurations
Содержание SIMATIC TD 200
Страница 22: ...1 12 SIMATIC TD 200 Operator Interface C79000 G7076 C272 01 Product Overview and Installation ...
Страница 84: ...A 12 SIMATIC TD 200 Operator Interface C79000 G7076 C272 01 Specifications and Reference ...
Страница 94: ...B 10 SIMATIC TD 200 Operator Interface C79000 G7076 C272 01 Multiple CPU Configurations ...
Страница 126: ...E 6 SIMATIC TD 200 Operator Interface C79000 G7076 C272 01 Modifying a TD 200 Configuration ...