4-5
SIMATIC TD 200 Operator Interface
C79000-G7076-C272-01
4.2
Using the Bar Graph Character Set
This sample program illustrates the bar graph character set. Version 1.1 and higher
of the TD 200 support creating a bar graph. Select the menu command Tools >
TD 200 Wizard..., as shown in Figure 4-1, and use the TD 200 Configuration
Wizard to make the following selections:
1. Select English, select bar graph character set.
2. Disable time-of-day menu, force menu, and password protection.
3. Reserve marker byte M0 for function keys, update as fast as possible.
4. Select one 40-character message.
5. Select the parameter block starting byte at VB0, message enables at VB12,
and message information at VB20.
6. Set message text: bbbbbbbbbbbbbbbbbbbb (where b is a blank)
BAR GRAPH SAMPLE
Figure 4-4 shows the data block generated in this sample.
// BEGIN TD200_BLOCK 0
// (Comments within this block should not be edited or removed)
VB0
’TD’
// TD 200 Identification
VB2
16#90
// Set Language to English, set Update to As fast as possible
VB3
16#01
// Set the display to 40 character mode; Up key V3.2; Down key V3.3
VB4
1
// Set the number of messages
VB5
0
// Set the Function Keys notification bits to M0.0 – M0.7
VW6
20
// Set the starting address for messages to VW20
VW8
12
// Set the starting address for message enable bits to VW12
// MESSAGE 1
// Message Enable Bit V12.7
VB20
’ BAR GRAPH SAMPLE ’
// END TD200_BLOCK 0
Figure 4-4 Data Block of the Bar Graph Sample Program
After you finish entering the parameters in the wizard, create the program shown in
Figure 4-5, download the data block and the program to a CPU, and place the
CPU in RUN mode. Adjust potentiometer 0 to display the bar graph.
Note
This example does not produce an exact representation of the analog
potentiometer value. The partial bars are approximate.
Creating Sample Programs
Содержание SIMATIC TD 200
Страница 22: ...1 12 SIMATIC TD 200 Operator Interface C79000 G7076 C272 01 Product Overview and Installation ...
Страница 84: ...A 12 SIMATIC TD 200 Operator Interface C79000 G7076 C272 01 Specifications and Reference ...
Страница 94: ...B 10 SIMATIC TD 200 Operator Interface C79000 G7076 C272 01 Multiple CPU Configurations ...
Страница 126: ...E 6 SIMATIC TD 200 Operator Interface C79000 G7076 C272 01 Modifying a TD 200 Configuration ...