Wiring
4.4 Module status after power is switched on
Counter module FM 450-1
34
Manual, 02/2014, A5E03648739-02
Digital outputs
For the purpose of directly initiating control processes, the FM 450-1 has the digital outputs
1Q0 and 1Q1 (for counter 1) or 2Q0 and 2Q1 (for counter 2) that are supplied via the load
voltage 2L+.
The digital inputs are potentially isolated from the S7-400 bus and count inputs.
The digital outputs are P switches and can carry a load current of 0.5 A. They are protected
against overload and short circuit.
Note
The direct connection of relays and cutouts can be executed without external wiring
The time-related behavior of the digital outputs depends on the parameter assignment and is
described in greater detail in the chapter "Setting: Behavior of the digital outputs (Page 76)".
2L+ /2M load voltage
To ensure the power supply of the digital outputs 1Q0 and 1Q1 or 2Q1 and 2Q2 you have to
connect a load voltage of 24 V to the module terminals 2L+ and 2M.
An integrated diode protects the module from reversing the polarity of the load voltage.
The 2L+ / 2M load voltage is not monitored by the FM 450-1.
Содержание simatic s7-400 FM 450-1
Страница 8: ...Table of contents Counter module FM 450 1 8 Manual 02 2014 A5E03648739 02 ...
Страница 18: ...Product Overview 1 5 The FM 450 1 software Counter module FM 450 1 18 Manual 02 2014 A5E03648739 02 ...
Страница 40: ...Wiring 4 4 Module status after power is switched on Counter module FM 450 1 40 Manual 02 2014 A5E03648739 02 ...
Страница 54: ...Program 6 5 Technical specifications of the blocks Counter module FM 450 1 54 Manual 02 2014 A5E03648739 02 ...
Страница 102: ...Encoder signals and their evaluation 9 5 Signal evaluation Counter module FM 450 1 102 Manual 02 2014 A5E03648739 02 ...
Страница 114: ...Errors and diagnostics 11 5 Operator error Counter module FM 450 1 114 Manual 02 2014 A5E03648739 02 ...
Страница 120: ...Spare parts Counter module FM 450 1 120 Manual 02 2014 A5E03648739 02 ...
Страница 122: ...References Counter module FM 450 1 122 Manual 02 2014 A5E03648739 02 ...
Страница 126: ...Glossary Counter module FM 450 1 126 Manual 02 2014 A5E03648739 02 ...
Страница 130: ...Index Counter module FM 450 1 130 Manual 02 2014 A5E03648739 02 ...