Technical Data
12.2 Technical Data
Counter module FM 450-1
118
Manual, 02/2014, A5E03648739-02
Data to the count signals and the digital inputs and outputs (applies to both counters)
Digital outputs
•
Supply voltage
2L+ / 2M
•
Electrical isolation
Yes, toward all others except the digital inputs
•
Output voltage
–
High signal "1"
–
Low signal "0"
Min. 2L+ - 1.5 V
Max. 3 V
•
Switching current
–
Nominal value
–
Range
0.5 A (Res./P.D. 5W Tungsten 24VDC)
5 mA to 0.6 A
•
Switching time
Max. 300 µs
•
Cutoff voltage (inductive)
Limited to 2L+ -39V
•
Short-circuit proof
Yes
Note
Other relevant data, e.g. environmental conditions, are listed in Manual /1/.
Содержание simatic s7-400 FM 450-1
Страница 8: ...Table of contents Counter module FM 450 1 8 Manual 02 2014 A5E03648739 02 ...
Страница 18: ...Product Overview 1 5 The FM 450 1 software Counter module FM 450 1 18 Manual 02 2014 A5E03648739 02 ...
Страница 40: ...Wiring 4 4 Module status after power is switched on Counter module FM 450 1 40 Manual 02 2014 A5E03648739 02 ...
Страница 54: ...Program 6 5 Technical specifications of the blocks Counter module FM 450 1 54 Manual 02 2014 A5E03648739 02 ...
Страница 102: ...Encoder signals and their evaluation 9 5 Signal evaluation Counter module FM 450 1 102 Manual 02 2014 A5E03648739 02 ...
Страница 114: ...Errors and diagnostics 11 5 Operator error Counter module FM 450 1 114 Manual 02 2014 A5E03648739 02 ...
Страница 120: ...Spare parts Counter module FM 450 1 120 Manual 02 2014 A5E03648739 02 ...
Страница 122: ...References Counter module FM 450 1 122 Manual 02 2014 A5E03648739 02 ...
Страница 126: ...Glossary Counter module FM 450 1 126 Manual 02 2014 A5E03648739 02 ...
Страница 130: ...Index Counter module FM 450 1 130 Manual 02 2014 A5E03648739 02 ...