RF600 system planning
4.6 Guidelines for electromagnetic compatibility (EMC)
RF600
System Manual, 09/2005 Edition, J31069 D0171-U001-A0-7618,
4-29
4.6.7
Cable shielding
Signal cables must be shielded in order to prevent coupling of interference.
The best shielding is achieved by installing the cables in steel tubes. However, this is only
necessary if the signal cable is routed through an environment prone to particular
interference. It is usually adequate to use cables with braided shields. In either case,
however, correct connection is vital for effective shielding.
Note
An unconnected or incorrectly connected shield has no shielding effect.
As a rule:
•
For analog signal cables, the shield should be connected at one end on the receiver side
•
For digital signals, the shield should be connected to the enclosure at both ends
•
Since interference signals are frequently within the HF range (> 10 kHz), a large-area HF-
proof shield contact is necessary
Figure 4-9
Cable shielding
The shielding bus should be connected to the control cabinet enclosure in a manner allowing
good conductance (large-area contact) and must be situated as close as possible to the
cable inlet. The cable insulation must be removed and the cable clamped to the shielding
bus (high-frequency clamp) or secured using cable ties. Care should be taken to ensure that
the connection allows good conductance.
Содержание SIMATIC RF660
Страница 5: ...Table of contents RF600 System Manual 09 2005 Edition J31069 D0171 U001 A0 7618 v ...
Страница 6: ......
Страница 16: ...System overview 3 1 RF System SIMATIC RF600 RF600 3 4 System Manual 09 2005 Edition J31069 D0171 U001 A0 7618 ...
Страница 66: ......
Страница 96: ...Appendix A 4 Training RF600 A 6 System Manual 09 2005 Edition J31069 D0171 U001 A0 7618 ...