● Simulate status information
● Run restart functions
NOTICE
Restart functions
Read the device manufacturer information on this.
6.2.2
Performing diagnostics
An example of diagnostics in the SIMATIC Manager and detailed diagnostics with SIMATIC
PDM is shown below.
Requirements
● FF devices have been created
● An online connection to the FF device can be established
Diagnostics in the SIMATIC Manager
1. In SIMATIC Manager, open the project in the process device network view.
2. Select the FF device.
3. Select the Edit > Object Properties menu command.
The "<Device name> – Properties" dialog box opens.
4. Open the "Diagnostics" tab.
5. Click the "Update Diagnostics" button.
An attempt is made to establish a connection to the FF device. The status of the FF device
is determined and displayed. The following information on FF device communication is
displayed:
– Communication
– Device status
– Last check
– Message text
Note
Offline status
The last updated status of the FF devices are shown in the following views in SIMATIC
Manager:
● Process device network view
● Process device plant view
Commissioning
6.2 Diagnostics
FOUNDATION Fieldbus
Commissioning Manual, 02/2015, A5E32711026-AC
65