5. Make your changes.
Note
A maximum of 24 characters is permitted for a symbol.
Example: Symbol = "Status_Measurement"
6. Select the Table > Save menu command.
5.4.5
Configuring interconnections to the FF devices
PCS 7 supports you during the configuration of FF devices by providing prepared templates
for different functions. In the CFC Editor, you will find the templates in catalog > "Libraries" >
tab, folder "PCS 7 AP Library V..."\Templates\Templates.
You can find information about this in the context-sensitive help for the templates and in the
Process Control System PCS 7; Advanced Process Library documentation.
Channel blocks for FF devices
Use the channel blocks of the PCS 7 Advanced Process Library (APL) to interconnect the
signals of FF devices.
Use one channel block for each I/O address.
Block type
Address range
Block name
Function block
Block I/O
Analog
Input
FbAnIn
FB 1813
PV
Output
FbAnOu
FB 1814
SP
Digital
Input
FbDiIn
FB 1815
PV
Output
FbDiOu
FB 1816
SP
Requirements
● FF devices have been configured.
● Symbols have been created.
Procedure
You have the following options for configuring interconnections:
● Configure the interconnections in the PCS 7 Import/Export Assistant using templates.
● Create your own CFC charts.
Additional information
You can find additional information and step-by-step instructions in the configuration manual
Process Control System PCS 7; Engineering System.
Engineering
5.4 Using the applications
FOUNDATION Fieldbus
Commissioning Manual, 02/2015, A5E32711026-AC
57
Содержание SIMATIC PCS 7 FOUNDATION Fieldbus
Страница 6: ...Security information FOUNDATION Fieldbus 6 Commissioning Manual 02 2015 A5E32711026 AC ...
Страница 10: ...Introduction FOUNDATION Fieldbus 10 Commissioning Manual 02 2015 A5E32711026 AC ...